Section 6: Commissioning
GROUP NAVIGATION

Figure 39: Drive Display

Leave all other settings not listed in the following table in their default values.

Table 14: Drive programming parameters

Parameter code
9902
9905
9906
9907
1103
1300
1301
1302
2007
2008
2102
2202
2203
2601
126
Description
Function select
Motor rated voltage
Motor rated current
Motor frequency
Command source mode
Analog input 1 signal format
Analog input 1 offset
Analog input 1 scaling
Min frequency limit
Max frequency limit
Stop mode
Accel time
Decel time
Energy optimizer
Issue date: 12/19/2023
PARAMETER STRUCTURE
Setting
0
See motor nameplate
(208 V, 230 V, 460 V)
See motor nameplate
See motor nameplate
(50 Hz, 60 Hz)
0
U 0-10
23.5
1850
0
See motor nameplate
(50 Hz, 60 Hz)
0
30.0
30.0
0
Form 150.72-ICOM6