Figure 33: Eight Fan Units Dimensions - Ylaa0155Zj - York YLAA0041 Installation Operation & Maintenance

Air-cooled scroll chillers with brazed plate heat exchanger style b (60 hz) 4 to 12 fan 40 ton to 230 ton 140 kw to 800 kw
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

Form 150.72-ICOM6
Issue date: 12/19/2023
Water connection sizes are shown in
Physical Data, see Table 5 on page
48
F
W
L
YLAA Model
(length)
(width)
YLAA0155SE
187.5
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control's unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6'; rear to wall – 6'; control panel to end wall – 4'0'';
top – no obstructions allowed; distance between adjacent units – 10'. No more than one adjacent wall may be higher than the unit.
Figure 33: Eight Fan Units Dimensions – YLAA0155ZJ
Johnson Controls
Eight fan units
YLAA0155ZJ
P
C1
W
H
F
(height)
88.3
94.2
88.5
R3
C2
L
P
D
C1
42.8
17.3
22
Section 5: Technical data
R1
R2
(TYP)
8Fan_assyax
C2
R3
R2
102
58
66
5 5
H
D
R1
39
107