Form 150.72-ICOM6
Issue date: 12/19/2023
Dimensions – YLAA0070SE, YLAA0080SE, YLAA0089SE
OPTIONAL
DISCONNECT SWITCH
(STANDARD ON CE)
141 [5.5] OR 226.9 [8.93]
DIMENTION VARIES BASED ON
CHILLER MODEL SELECTED
2242 [88.3]
FRAME WIDTH
2256 [88.8]
OVERALL WIDTH
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control's unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
Figure 27: Four Fan Units Dimensions – YLAA0070SE, YLAA0080SE, YLAA0089SE
Johnson Controls
Four fan units
51.4 [2.02]
(OPTIONAL HEAT
RECOVERY UNIT)
741 [29.2]
588 [23.2]
1735 [68.3]
495 [19.5]
1921 [75.6]
2547 [100.3]
WATER CONNECTIONS
2994 [117.9]
OVERALL LENGTH
1678 [66.1]
1117 [44.0]
3" VICTAULIC
OUTLET
3" VICTAULIC
INLET
3" VICTAULIC
INLET
16mm [5/8"]
MOUNTING
HOLES TYP
2911 [114.6]
FRAME LENGTH
Section 5: Technical data
035-24059-002 REV-E
POWER ENTRY
330.2 [13.00] WIDE X 177.8 [7.00] HIGH
(190mm x 120mm EUROPEAN BUILD)
1177 [46.4]
(1298mm EUROPEAN BUILD)
CONTROL PANEL BOTTOM DETAIL
36 [1.4]
269 [10.6]
MOUNTING
WATER CONNECTIONS
HOLES TYP
36 [1.4]
MOUNTING
HOLES TYP