Handling And Safety Instructions - SolarEdge TerraMax SE330K Series Quick Installation Manual

Hide thumbs Also See for TerraMax SE330K Series:
Table of Contents

Advertisement

Legend
NOTE
This symbol denotes information intended to assist the user
in making optimum use of the product.
CAUTION!
Denotes a hazard. It calls attention to a procedure that, if
not correctly performed or adhered to, could result in
damage or destruction of the product. Do not proceed
beyond a caution sign until the indicated conditions are
fully understood and met.
WARNING!
!
Denotes a hazard. It calls attention to a procedure that, if
not correctly performed or adhered to, could result in
injury or loss of life. Do not proceed beyond a warning
note until the indicated conditions are fully understood
and met.
Do not cut the cable connectors
Do not bend the cable. Bending radius: 4 x wire diameter.
This symbol appears at grounding points on the SolarEdge
manuals and equipment.
SAVE THESE INSTRUCTIONS – This guide contains important instructions for
SolarEdge TerraMax Inverter that should be followed during installation and
maintenance. Using this equipment in a manner not specified in this guide by
SolarEdge may impair the protection provided by this equipment.
Turn ON/OFF the main circuit board AC switch.
ON
When turning it off, wait 5 minutes for DC
Voltage to drop to a safe level before removing
the front panel.
OFF
Turn the DC Disconnect Switch on/off. (Switch is
OFF
available for some models)
When turning it off, wait 5 minutes for DC
ON
Voltage to drop to a safe level before removing
the front panel.
Turn the ON/OFF/P Switch on/off. When turning
ON (1)
OFF (0)
it off, wait 5 minutes for DC Voltage to drop to a
safe level before removing the front panel.
P 1 0
P 1 0
Before connecting aluminum wires to terminals:
1. Remove oxide from the exposed wires with emery paper or a
steel wire brush
2. Clean dust with a cloth and Isopropyl alcohol (IPA)
3. Coat wires with a designated antioxidant aluminum wire
grease immediately after cleaning
CAUTION! Connection of oxidized aluminum wires may result
in resistance and high temperatures at contact points.