Immergas VICTRIX HYBRID PLUS Manual page 84

Hide thumbs Also See for VICTRIX HYBRID PLUS:
Table of Contents

Advertisement

Victrix Plus 24HY
Gas type
G20
G31
Gas type
G20
If a Hydrogen ready installation is planned for H
ing to local standards in force) all calibration of the unit must refer to the O
In addition to yearly maintenance, one must also check the energy efficiency of the thermal system, with frequency and proce-
dures that comply with the indications of the technical regulations in force.
When adjusting nominal heat input, if the O
adjustments are required.
84
CO
to Nominal Q.
2
9,7 (9,5 ÷ 10,2)
11,4 (11,1 ÷ 11,5)
O
at Nominal Q.
2
3,5 (3,9 ÷ 2,6)
values are not reached with the gas flow regulator completely open, no further
2
CO
to ignition Q.
2
9,7 (9,5 ÷ 10,2)
11,4 (11,1 ÷ 11,5)
O
at Ignition Q.
2
3,5 (3,9 ÷ 2,6)
percentages up to 20%, (referring to the gas distributed in the network accord-
2
values in the table above.
2
CO
to Minimum Q.
2
8,8 (8,5 ÷ 9,0)
10,6 (10,5 ÷ 10,9)
O
at Minimum Q.
2
5,1 (5,7 ÷ 4,8)

Advertisement

Table of Contents
loading

This manual is also suitable for:

3.030699