Outdoor Unit Technical Data Table - Immergas VICTRIX HYBRID PLUS Manual

Hide thumbs Also See for VICTRIX HYBRID PLUS:
Table of Contents

Advertisement

4.4

OUTDOOR UNIT TECHNICAL DATA TABLE

The data shown below refer to the Audax.DK4 outdoor unit.
Nominal data for low temperature applications *
Nominal central heating output
Absorption
COP
Nominal data for intermediate temperature applications (A35/W7) **
Nominal central heating output
Absorption
COP
Nominal data for medium temperature applications *
Nominal central heating output
Absorption
COP
* Central heating mode status: heat exchanger water inlet/remains at 30 °C/35 °C, outdoor air temperature 7 °C db/6 °C wb. Performance
in compliance with EN 14511.
* Central heating mode status: heat exchanger water inlet/remains at 40 °C/45 °C, outdoor air temperature 7 °C db/6 °C wb.
*** Central heating mode status: inlet/remains at 47 °C/55 °C, outdoor air temperature 7 °C db/6 °C wb. Performance in compliance with
EN 14511.
Outdoor unit data.
Ambient operating temperature range
Water content
Central heating circuit maximum operating pressure
Minimum installation temperature
Electrical connection
Power supply frequency
Maximum input
Electric plant protection
Empty outdoor unit weight
Full outdoor unit weight
Type of refrigerant
Quantity of refrigerant
GWP
tCO2eq
Ps Max
Ps Min
116
Audax.DK4
kW
kW
kW
kW
kW
kW
Audax.DK4
°C
l
bar
°C
Vac
Hz
A
-
kg
kg
-
g
-
-
Mpa
Mpa
3,83
0,85
4,49
3,80
1,15
3,30
3,28
1,29
2,56
-14 ... +35
2
4
-25
220-240
50
10,3
IPX4
45
47
R-32
560
675
0.38
4,17
2,76