Programming The P.c.b - Immergas VICTRIX EXA 24 X 1 ERP Instruction Booklet And Warning

Table of Contents

Advertisement

3.11 PROGRAMMING THE P.C.B.

The boiler is prepared for possible programming of several op-
eration parameters. By modifying these parameters as described
below, the boiler can be adapted according to specific needs.
To access the programming stage, set the DHW selector (5) in
the "6" position and the heating selector (6) in the "9" position
and press the "Reset" (3) and "Summer/Winter" (2) buttons for
about 8 seconds.
Once the menu has been accessed, it is possible to scroll through
the three sub-menus present (s, p, t) by pressing the "Summer/
Winter" (2) button for 1 second.
Id
Parameter
Parameter
Minimum DHW
S0
output
Maximum DHW
S1
output
Minimum CH
S2
output
Maximum CH
S3
output
Power
S4
block
Central heating
S5
set point mini-
mum temperature
Central heating
S6
set point maxi-
mum temperature
External probe
S7
correction
S8
Boiler power
52
Description
The boiler also has electronic modulation that adapts the boiler poten-
tiality to the effective heating demand of the house. Therefore the boiler
works normally in a variable gas pressure field between minimum and
maximum power depending on the system heat load, setting fan speed
(in rpm, hundreds of revs are represented on the display).
N.B.: the boiler is produced and calibrated in the central heating phase
at nominal output. Approximately 10 minutes are needed to reach the
nominal heat output, which can be changed using the parameter (S3).
N.B.: selection of parameters in the presence of requests, allows boiler
functioning with current equal to the respective value.
Defines the minimum flow temperature.
Defines the maximum flow temperature.
If the reading of the external probe is not correct it is possible to correct
it in order to compensate any environmental factors.
(Over the value of +9 the display shows "CE", which enables an external
control function of the boiler for coupling of the same with a system
supervisor)
Identifies the boiler s power (only useful with a coupled storage tank
and parameter P0=1).
Use the ''D.H.W. regulator'' selector (5) to select the parameter
(within the same sub-menu) and rotate the ''C.H. regulator''
selector (6) to modify the value according to the range available.
Press the "Reset" (3) button for 1 second to store the altered
parameters.
If the parameters are stored successfully, "88" appears on the
indicator (14) for 2 seconds.
Exit the programming mode by waiting for 15 minutes or by
pressing the "Reset" (3) and "Summer/Winter" (2) buttons at the
same time.
900 ÷ 1500
3500 ÷ 6100
1500 ÷ 3500
(S5+5) ÷ 85
1 = 26 kW
Personalized
Range
Default
1400
G20 = 4600
G31 = 4600
S0 ÷ S3
1400
S2 ÷ S1
4600
2000
20 ÷ 50 °C
20
85
°C
-9 ÷ 9 K
0
0 = 12 kW
1
2 = 28 kW
3 = 32 kW
value