Immergas VICTRIX EXTRA 12 PLUS Instructions And Recommendations page 81

Table of Contents

Advertisement

Victrix Extra 12 Plus
Gas type
G20
G31
Gas type
G20
Victrix Extra 24 Plus
Gas type
G20
G31
Gas type
G20
Victrix Extra 35 Plus
Gas type
G20
G31
Gas type
G20
If a Hydrogen ready installation is planned for H
ing to local standards in force) all calibration of the unit must refer to the O
In addition to yearly maintenance, one must also check the energy efficiency of the thermal system, with frequency and proce-
dures that comply with the indications of the technical regulations in force.
In the setting at Q. Nominal and at Q. Minimum, if the O
repeated. If after this operation the values are still not within the indicated ranges, no further adjustments are necessary.
In the case of an annual inspection of the device, the max CO must be less than 700 ppm (0% O
device requires maintenance/repair.
CO
to nominal Q.
2
8,8 (8,3 ÷ 9,3) %
10,0 (9,5 ÷ 10,5) %
O
at Nominal Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to nominal Q.
2
8,8 (8,3 ÷ 9,3) %
10,0 (9,5 ÷ 10,5) %
O
at Nominal Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to nominal Q.
2
8,8 (8,3 ÷ 9,3) %
10,0 (9,5 ÷ 10,5) %
O
at Nominal Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to ignition Q.
2
8,8 (8,3 ÷ 9,3) %
10,0 (9,5 ÷ 10,5) %
O
at Ignition Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to ignition Q.
2
8,8 (8,3 ÷ 9,3) %
10,0 (9,5 ÷ 10,5) %
O
at Ignition Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to ignition Q.
2
8,8 (8,3 ÷ 9,3) %
10,0 (9,5 ÷ 10,5) %
O
at Ignition Q.
2
5,1 (6,0 ÷ 4,2) %
percentages up to 20%, (referring to the gas distributed in the network accord-
2
values in the table above.
2
values are not reached, the Automatic Calibration procedure must be
2
CO
to minimum Q.
2
8,8 (8,3 ÷ 9,3) %
9,5 (9,0 ÷ 10,0) %
O
at Minimum Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to minimum Q.
2
8,8 (8,3 ÷ 9,3) %
9,5 (9,0 ÷ 10,0) %
O
at Minimum Q.
2
5,1 (6,0 ÷ 4,2) %
CO
to minimum Q.
2
8,8 (8,3 ÷ 9,3) %
9,5 (9,0 ÷ 10,0) %
O
at Minimum Q.
2
5,1 (6,0 ÷ 4,2) %
). If the CO value is higher, the
2
81