Creating an Ethernet (LAN) Connection
NOTE
If using a cable longer than 10 m / 33 ft in areas where there is a risk of induced
voltage surges by lightning, it is recommend to use external surge protection
devices.
For details refer to:
protection.pdf.
To connect the Ethernet cable:
 1.  Remove the inverter cover as described in Removing the Inverter Cover on page 46.
 2.  Open the communication gland.
CAUTION!
The gland includes a rubber waterproof fitting, which should be used to ensure proper sealing.
 3.  Remove the plastic seal from one of the large openings.
 4.  Remove the rubber fitting from the gland and insert the CAT5/6 cable through the gland and through 
the gland opening in the inverter.
 5.  Push the cable into the cut opening of the rubber fitting.
 
CAT5/6 standard cables have eight wires (four twisted pairs), as shown in the diagram below. Wire colors 
may differ from one cable to another. You can use either wiring standard, as long as both sides of the 
cable have the same pin-out and color-coding.
RJ45 Pin #
1
2
3
4
5
6
7
8
1 The inverter connection does not support RX/TX polarity change. Supporting crossover Ethernet cables depends on the
switch capabilities.
48
Single Phase Inverter with HD-Wave Technology Installation MAN-01-250-1.2
http://www.solaredge.com/files/pdfs/lightning_surge_
Figure 18: Communication gland and rubber fitting
Wire Color
T568B
White/Orange
Orange
White/Green
Blue
White/Blue
Green
White/Brown
Brown
1
T568A
White/Green
Green
White/Orange
Blue
White/Blue
Orange
White/Brown
Brown
10Base-T Signal
100Base-TX Signal
Transmit+
Transmit-
Receive+
Reserved
Reserved
Received-
Reserved
Reserved