Inverter Configuration – Setup Mode
Inverter Configuration – Setup Mode
After inverter installation, an installer may perform basic system configuration. Configuration is done 
when the inverter is in Setup mode.
To enter Setup mode:
 1. Turn the inverter ON/OFF switch to OFF (AC remains ON).
WARNING!
If the inverter was operating properly (power was produced by the power optimizers), the
following message is displayed.
This message is displayed until the DC voltage is safe (50V). Do not open the cover until the
voltage is safe or until at least five minutes have passed.
 2. Press the OK button for at least 5 seconds. The following message is displayed:
P l e a s e
P a s s w o r d
* * * * * * * *
 3. Press the Up, Down and OK buttons (Up=1, Down=2, OK=3) for entering the Setup mode password:
pq OK pqOK pq (12312312).
The   i nverter is now in Setup mode and all its LEDs are lit. The   i nverter automatically exits Setup mode if no 
buttons are pressed for more than 2 minutes.
The following shows a hierarchical tree of the menu options, which are described in Configuration Menu 
Options on page 34. Actual menus may vary from shown depending on the firmware version of the 
inverter and on the country.
Main menu:
Country:
G e r m a n y +
S p a i n
F r a n c e
.
.
.
Language:
E n g l i s h
G e r m a n
S p a n i s h
F r e n c h
I t a l i a n
32
Single Phase Inverter with HD-Wave Technology Installation MAN-01-250-1.2
D C
V O L T A G E
D O
N O T
D I S C O N N E C T
V D C :
7 2 . 0
e n t e r
N O T
S A F E