Installation Guidelines

 
Frame-mounted power optimizers are mounted directly on the module frame , 
l
regardless of racking system (rail-less or with rails). For installation of frame-mounted 
power optimizers, refer to http://www.solaredge.com/sites/default/files/installing_
frame_mounted_power_optimizers.pdf.
 
The steps in this chapter refer to module add-on power optimizers. For smart 
l
modules, start from Step 3: Connecting Power Optimizers in Strings on page 17 . Also 
refer to the documentation supplied with the smart modules.
 
The power optimizer can be placed in any orientation.
l
 
If connecting more modules than optimizer inputs in parallel, use a branch cable. Some commercial 
l
power optimizer models     h ave a dual input.
 
Position the power optimizer close enough to its module so that their cables can be connected.
l
 
Make sure to use power optimizers that have the required output conductor length:
l
 
Minimize the use of extensions between power optimizers.
o
 
You can use extension cables between rows and from the end of string to the inverter.
o
 
Do not use extension cables between the modules and the power optimizers, or between two 
o
power optimizers within a string.
 
The minimum and maximum string length guidelines are stated in the power optimizer datasheets. 
l
Refer to the   D esigner for string length verification. The   D esigner is available on the SolarEdge website 
at http://www.solaredge.com/products/installer-tools/site-designer#/.
 
Completely shaded modules may cause their power optimizers to temporarily shut down. This will 
l
not affect the performance of the other power optimizers in the string, as long as the minimum 
number of unshaded power optimizers connected in a string of modules is met. If under typical 
conditions fewer than the minimum optimizers are connected to unshaded modules, add more 
optimizers to the string.
 
                                 T o allow for heat dissipation, maintain a 2.5 cm / 1" clearance distance between the power optimizer 
l
and other surfaces, on all sides except the mounting bracket side. 
NOTE
The images contained herein are for illustrative purposes only and may vary depending on product
models.
Single Phase Inverter with HD-Wave Technology Installation MAN-01-250-1.2
Figure 2: Power optimizer clearance
Chapter 2: Installing the Power Optimizers
15