List of outdoor unit anomalies
If the outdoor unit is faulty, the error code is signalled on the control panel (Fig. 23) and on the interface board (see paragraph "Interface
board - 7-segment display"). The failure is signalled in different ways.
On the control panel, the error is displayed with an "A" + error code.
On the interface board, the error is displayed with an "E" + error code, showing a sequence of two digits.
For example:
Error 101 is displayed as follows: E1 alternated with 01.
The following is the list of alarms as displayed on the control panel.
Error Code
A101
Outdoor unit communication error
Communication error due to incorrect address of
A109
interface board
MODBUS communication error
A122
EEPROM error
A162
A177
Emergency error
A198
Error of thermal fuse terminal board (open)
Communication error (failed coupling) between
A201
interface board and outdoor unit
Communication error (failed coupling) between
A202
indoor unit and interface board
Communication error between Inverter and main
A203
board of the outdoor unit
Outdoor unit air temperature sensor error
A221
A231
Condenser temperature sensor error
Discharge temperature sensor error
A251
(1) If the shutdown or fault persists, contact an authorised company (e.g. Authorised After-Sales Technical Assistance Centre).
Anomaly signalled
Indoor unit status / Solution
Check the communication cable to the outdoor unit. Check that
the interface board works properly.
(1)
Check the address on the interface board.
(1)
Check communication between the management board and inter-
face boards.
(1)
Replace the main board of the outdoor unit
(1)
(1)
(1)
Check the communication cable to the outdoor unit.
Check that the interface board and main board of the outdoor unit
work properly
(1)
Check the communication cable to the outdoor unit.
Check that the interface board and main board of the outdoor unit
work properly
(1)
Check wiring of communication between the two boards.
Replace the main board.
Replace the inverter board
(1)
Check the position of the sensor.
Check the relative wiring
Replace the sensor
(1)
Check the position of the sensor.
Check the relative wiring
Replace the sensor
(1)
Check the position of the sensor.
Check the relative wiring
Replace the sensor
41