1.12 REMOTE ZONE CONTROL (OPTIONAL)

This remote device is used to adjust the setpoints and to view the main information of the zone where it was configured.
Connect the appliance as shown (Fig. 9);
When the connections are complete, switch off and re-power the appliance.
To correctly configure the device, set the parameters as described below:
Assistance Menu -> Device configuration
Slave address: Address to configure according to the zone where the device is installed
Baud Rate
Parity bit
Stop bits
Heat pump control
Using a Zone Remote Panel with firmware version 2.00 or higher:
- the item "Head pump control" is no longer present;
- it is possible to enable room probe modulation;
- the dew point control can be enabled.
For correct operation it is necessary to install the jumper on the thermostat of the zone associated to the panel.
If necessary, this jumper can be replaced with a safety thermostat.
A restart of the machine is recommended after connecting the remote panel.

1.13 DOMINUS (OPTIONAL)

The system can be remote controlled using the optional Dominus kit.
Connect the appliance as shown (Fig. 9);
The following is necessary to enable Dominus:
- position the Dip Switches: OFF-OFF-OFF-ON;
- set the A30 parameter on the control panel = ON;
- configure the Dominus APP profile on Magis Pro-Combo V2.
The Dominus firmware must be updated to at least revision 2.02.
For further information, consult the relative instruction sheet.

1.14 HUMIDISTAT ON/OFF (OPTIONAL)

You can make a dehumidification demand by using a humidistat.
Connect the appliance as shown (Fig. 9);
22
Zone 1 = 41
Zone 2 = 42
Zone 3 = 43
9600
Even
1
NO