1.11 MODBUS TEMPERATURE AND HUMIDITY ROOM PROBES (OPTIONAL)

The temperature and humidity probe is used to detect room humidity and to calculate the relative dew point by regulating the flow tem-
perature during the cooling phase.
Connect the appliance as shown (Fig. 9);
DIP-Switch configuration table
DIP 1-5
(Address)
DIP 6-7
(Type)
DIP 8
(Speed)
DIP 1-5
ON
1
2
3
ON
1
ON
1
ON
1
DIP 6-7
4
5
6
2
3
4
5
2
3
4
5
2
3
4
5
ON
6
7
ON
8
DIP 8
7
8
Zone 1 (Address 131)
Zone 2 (Address 132)
Zone 3 (Address 133)
Modbus 1 - 8 - E - 1
9600 bit/s
21