Instructions For Maintenance And Initial Check; General Warnings; Initial Check - Immergas MINI EOLO X 24 3 E Instructions And Warnings

Hide thumbs Also See for MINI EOLO X 24 3 E:
Table of Contents

Advertisement

3
INSTRUCTIONS FOR
MAINTENANCE AND

INITIAL CHECK.

3.1

GENERAL WARNINGS.

ATTENTION:
operators who install and service the
appliance must wear the personal pro-
tective equipment (PPE) required by
applicable law.
Note: the list of possible PPE is not
complete as they are indicated by the
employer.
ATTENTION:
before performing any maintenance
operation, make sure:
- you have disconnected the power to
the appliance;
- you have closed the gas cock;
- you have discharged the pressure
from the system and domestic hot
water circuit.
Supply of spare parts.
The device's warranty shall be rendered null and void
if unapproved or unsuitable parts are used for main-
tenance or repairs. These will also compromise the
product's compliance, and the said product may no
longer be valid and fail to meet the current regulations.
With regard to the above, only use Immergas original spare
parts when replacing parts.
If additional documentation needs to be consulted for
extraordinary maintenance, contact the Authorised
After-Sales Service.
36
3.2
INITIAL CHECK.
To commission the boiler:
- ensure that the declaration of conformity of instal-
lation is supplied with the appliance;
- make sure that the type of gas used corresponds to
boiler settings (the type of gas is displayed on the
data nameplate and in the relevant P01 parameter);
- check connection to a 230V ~ 50Hz power mains, correct
L-N polarity and the earthing connection;
- make sure the central heating system is filled with water and
that the boiler manometer indicates a pressure of 1÷1.2 bar;
- make sure the air valve cap is open and that the system is well
deaerated;
- switch the boiler on and ensure correct ignition;
- check the CO
flow rate in the flue:
2
• maximum;
• minimum;
- the values comply with the relevant tables (Par. 3.3);
- check activation of the safety device in the event of no gas, as
well as the relative activation time;
- check activation of the main switch located outside the boiler;
- check that the intake and/or exhaust terminals are not
blocked;
- check activation of the "no air" safety pressure switch;
- ensure activation of all adjustment devices;
- seal the gas flow regulation devices (if the settings are
changed);
- ensure production of domestic hot water (when the boiler is
connected to an external cylinder);
- check the tightness of the hydraulic circuits;
- check ventilation and/or aeration of the installation room
where provided.
Even if just one single safety check provides a negative result,
do not commission the system.