Separator Kit Installation - Immergas MINI EOLO X 24 3 E Instructions And Warnings

Hide thumbs Also See for MINI EOLO X 24 3 E:
Table of Contents

Advertisement

1.16 SEPARATOR KIT INSTALLATION.

• Type C configuration, sealed chamber and fan assisted.
This kit allows air to come in from outside the building and the
exhaust to exit from the chimney or flue through divided flue
exhaust and air intake pipes. Combustion products are expelled
from pipe (S). The required amount of air is taken in through
pipe (A) for combustion. The intake pipe (A) can be installed
either on the right or left hand side of the central exhaust pipe
(S). Both ducts can be routed in any direction.
Please note the type of installation C
ural draught flue. Moreover, with C
exhaust pipes cannot be installed on opposing walls.
• Separator kit Ø 80/80.
Kit assembly (Fig. 24): install flange (4) on the central hole of
the boiler, fitting gasket (1) and tighten with the flat-tipped
hex screws included in the kit. Remove the flat flange present
in the lateral hole with respect to the central one (according to
needs) and replace it with the flange (3), positioning the gasket
(2) already present in the boiler and tighten using the supplied
self-threading screws. Fit the male end (smooth) to the bends
(5) in the female end of the flanges (3 and 4). Fit the intake ter-
minal (6) with the male section (smooth) in the female section
of the bend (5) up to the stop, ensuring that the internal and
external wall sealing plates are fitted. Fit the exhaust pipe (9)
9
S
7
4
1
The kit includes:
N°1 - Exhaust gasket (1)
N°1 - Female intake flange (3)
N°1 - Flange gasket (2)
N°1 - Female exhaust flange (4)
** The configuration on walls
opposite the building is not allowed.
22
must be done with a nat-
4
configuration, intake and
5
5
6
7
5
A
3
2
N°2 - 90° bend Ø 80 (5)
N°1 - Intake terminal Ø 80 (6)
N°2 - Internal wall sealing plates (7)
N°1 - External wall sealing plate (8)
N°1 - Exhaust pipe Ø 80 (9)
C
52
26
with the male end (smooth) to the female end of the bend (5) up
to the stop; making sure that the internal wall sealing plate has
been fitted. This will ensure sealing and joining of the elements
making up the kit.
• Installation clearances. Figure 25 gives the min. installation space
dimensions of the Ø  80/80 separator terminal kit in limited
conditions.
• Figure 26 shows the configuration with vertical exhaust and
horizontal intake.
• Extensions for the separator kit Ø 80/80. The max. vertical
straight length (without bends) that can be used for Ø 80 intake
and exhaust pipes is 41 metres of which 40 intake and 1 exhaust.
The total length corresponds to a resistance factor of 100. The
total usable length obtained by adding the length of the intake
and exhaust pipes Ø 80, must not exceed the values stated in
the following table. If mixed accessories or components are used
(e.g. changing from a separator Ø 80/80 to a concentric pipe),
the maximum extension can be calculated by using a resistance
factor for each component or the equivalent length. The sum of
these resistance factors must not exceed 100.
C
* Configuration C
82
working with natural draught.
8
24
envisages connection to flues
4
C
42
25
C
82
27