1.15 CONCENTRIC VERTICAL KIT INSTALLATION.

• Type C configuration, sealed chamber and fan assisted.
Concentric vertical intake and exhaust kit. This vertical terminal
is connected directly to the outside of the building for air intake
and flue exhaust.
The vertical kit with aluminium tile enables installation
on terraces and roofs with a maximum slope of 45%
(approx 25°) and the height between the terminal cap
and half-shell (374 mm) must always be observed.
• Vertical kit with aluminium tile Ø 80/125.
Kit assembly (Fig. 22): install the concentric flange (2) on the
central hole of the boiler inserting the gasket (1) and tighten
using the screws in the kit. Fit the male end (smooth) of the
adapter (3) into the female end of the concentric flange (2).
Imitation aluminium tile installation. Replace the tile with the
aluminium sheet (5), shaping it to ensure that rainwater runs
off. Position the fixed half-shell (7) on the aluminium tile and
insert the intake-exhaust pipe (6). Fit the Ø 80/125 concentric
terminal pipe with the male end (6) (smooth) to the female end
of the adapter (3) (with lip gasket) up to the stop; making sure
that the wall sealing plate has been fitted, this will ensure sealing
and joining of the elements making up the kit.
8
5
4
6
3
2
1
The kit includes:
7
N°1 - Gasket (1)
N°1 - Female flange
concentric (2)
N°1 - Adapter Ø 60/100)
for Ø 80/125 (3)
N°1 - Wall sealing plate (4)
N°1 - Aluminium tile (5)
N°1 - Concentric pipe
int./exh. Ø 80/125 (6)
N°1 - Fixed half-shell
N°1 - Mobile half-shell
The vertical kit with this configuration can be extended up to a
maximum of 12,200 mm vertical rectilinear, with the terminal
included (Fig. 23). This configuration corresponds to a resist-
ance factor of 100. In this case the special extensions must be
requested.
The terminal Ø 60/100 can also be used for vertical exhaust,
in conjunction with concentric flange code 3.011141 (sold
separately).
The vertical kit with this configuration can be extended up to
a maximum of 4,700 mm vertical rectilinear, with the terminal
included (Fig. 23).
C
32
22
C
32
23
21