1.14 INDOOR INSTALLATION.

• Type C configuration, sealed chamber and fan assisted.
Installation of this terminal is governed by standards contained
in local building regulations, as amended.
In addition to the traditional "Ø60/100 horizontal kit"
there is also a specific "Ø60/100 Star" version, with the
same measurements and equivalent head loss.
This terminal is connected directly to the outside of the building
for air intake and flue exhaust. The horizontal kit can be installed
with the rear, right side, left side or front outlet.
• External grid. N.B.: for safety purposes, do not obstruct the
boiler intake-exhaust terminal, even temporarily.
• Horizontal intake - exhaust kit Ø 60/100.
Kit assembly (Fig. 15): install the bend with flange (2) onto the
central hole of the boiler inserting the gasket (1) and tighten
using the screws in the kit. Couple the terminal pipe (3) with
the male end (smooth) into the female end of the bend (with lip
seals) up to the stop; making sure that the internal wall sealing
plate and external wall sealing plate have been fitted, this will
ensure sealing and joining of the elements making up the kit.
2
3
1
MAX. 725
4 5
The kit includes:
N°1 - Gasket (1)
N°1 - Concentric bend 90° (2)
N°1 - Intake/Exhaust concentric pipe
Ø 60/100 (3)
N°1 - Internal wall sealing plate (4)
N°1 - External wall sealing plate (5)
MAX. 645
• Application with rear outlet (Fig. 16). The 970 mm pipe length
enables routing through a maximum thickness of 770 mm. Nor-
mally the terminal must be shortened. Calculate the distance by
adding the following values: Part thickness + internal projection
+ external projection. The minimum indispensable projection
values are given in the figure.
• Application with side outlet (Fig. 17); Using the horizontal in-
take-exhaust kit, without the special extensions, enables routing
through a wall thickness of 725 mm with the left side outlet and
645 with the right side outlet.
• Extensions for horizontal kit. The horizontal intake-exhaust kit Ø
60/100 can be extended up to a max. horizontal distance of 3,000
mm including the terminal with grid and excluding the concen-
tric bend leaving the boiler. This configuration corresponds to
a resistance factor of 100. In these cases the special extensions
must be requested.
Connection with N°1 extension (Fig. 18). Max. distance between
vertical boiler axis and external wall is 1855 mm.
Connection with N°2 extensions (Fig. 19). Max. distance between
vertical boiler axis and external wall is 2805 mm.
C
12
15
C
12
17
Max. 770
Max. 1870
Max. 1855
Max. 2820
Max. 2805
C
12
16
C
12
18
C
12
19
19