1.13 OUTDOOR INSTALLATION IN PARTIALLY
PROTECTED AREA.
A partially protected location is a place where the
appliance is not exposed to the direct effects of the
weather (rain, snow, hail, etc.).
If the appliance is installed in a place where the am-
bient temperature drops below 0°C, use the optional
antifreeze kit, checking the ambient operating tem-
perature range shown in the technical data table in
this instruction booklet.
• Configuration type B, open chamber and fan assisted.
The relevant terminal must be used for this configuration (pres-
ent in the intake kit for the installation in question), which must
be placed on the central hole of the boiler (Fig. 13). Air intake
takes place directly from the environment in which the boiler
is installed and flue exhaust in individual flue or to the outside.
In this configuration the boiler is classified as type B
18
With this configuration:
- air intake takes place directly from the environment in which
the appliance is installed (external);
- the flue exhaust must be connected to its own individual flue
or channelled directly into the external atmosphere.
The technical regulations in force must be respected.
• Max. length of exhaust duct.
The flue pipe (vertical or horizontal) can be extended to a max.
length of 12 m straight route, using insulated pipes (Fig. 30). To
prevent problems of fume condensate in the exhaust pipe Ø 80,
due to fume cooling through the wall, the length of the pipe (not
insulated) must be limited to just 5 m.
Example of installation with direct vertical terminal in par-
tially protected location. When the vertical terminal for direct
discharge of combustion fumes is used, a minimum gap of 300
mm must be left between the terminal and the balcony above. The
height X+Y+Z+W evaluated with respect to the balcony above,
must be equal to or more than 2000 mm (Fig. 14). The term W
.
must only be considered if the balcony above has closed balustrade
22
(W=0 if the balustrade is open).
• Configuration without cover kit (boiler type C).
By leaving the side plugs fitted, it is possible to install the appli-
ance externally, in partially covered places, without the cover
kit. Installation takes place using the Ø60/100 and Ø80/125
concentric horizontal intake/ exhaust kits. Refer to the paragraph
relative to indoor installation. In this configuration the upper
cover kit guarantees additional protection for the boiler. It is
recommended but not compulsory.
• Fitting the cover kit.
To assemble and configure the cover kit correctly, please refer
to the relative instructions sheet.
12
13
VERTICAL TERMINAL KIT
FOR DIRECT DRAINING
INTAKE
COVER KIT
14