Creating An Rs485 Bus Connection - SolarEdge StorEdge SE7600A-USS Installation Manual

Hide thumbs Also See for StorEdge SE7600A-USS:
Table of Contents

Advertisement

 7.  For the switch/router side, use a pre-crimped cable or use a crimper to prepare an RJ45 
communication connector: Insert the eight wires into the RJ45 connector in the same order as above 
(Figure 34). 
 8.  Connect the cable RJ45 connector to the RJ45 port of the Ethernet switch or router. 
You can connect more than one inverter to the same switch/router or to different switches/routers, 
as needed. Each inverter sends its monitored data independently to the SolarEdge monitoring portal.
 9.  The inverter is configured by default to LAN. If   r econfiguration is required:
 a.  Make sure the ON/OFF switch is OFF.
 b.  Turn ON the AC to the inverter by turning ON the circuit breaker on the main distribution panel.
 c.  Turn ON the Safety Switch.
WARNING!
ELECTRICAL SHOCK HAZARD. Do not touch uninsulated wires when the inverter cover
is removed.
RISQUE D'ÉLECTROCUTION, ne touchez pas les fils non isolés lorsque le couvercle de
l'onduleur est retiré.
 d.  Use the internal user buttons to configure the connection, as described in Communication on 
page 45.
NOTE
If your network has a firewall, you may need to configure it to enable the connection to the
following address:
 10.  Verify the connection, as described in Verifying the Connection on page 78.

Creating an RS485 Bus Connection

The RS485 option enables creating a bus of connected inverters, consisting of up to 31 slave inverters and 
1 master inverter. Using this option, inverters are connected to each other in a bus (chain), via their 
RS485 connectors. The first and last inverters in the chain must be terminated.
RS485 wiring specifications:
 
Cable type: Min. 3-wire shielded twisted pair (a 4-wire cable may be used)
l
 
Wire cross-section area: 0.2- 1 mm²/ 24-18 AWG (a CAT5 cable may be used)
l
 
Maximum nodes: 32
l
 
Maximum distance between first and last devices: 1 km /3300 ft. 
l
NOTE
If using a cable longer than 10 m/33 ft in areas where there is a risk of induced voltage surges by
lightning, it is recommend to use external surge protection devices. For details refer to:
http://www.solaredge.us/files/pdfs/lightning_surge_protection.pdf.
used for routing the communication wires, there is no need for a lightning protection device.
NOTE
If a revenue grade meter is connected to your inverter, it uses the RS485 port and therefore an
RS485 communication bus cannot be created.
The following sections describe how to physically connect the RS485 bus and how to configure the bus.
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
Destination Address: prod.solaredge.com
l
TCP Port: 22222 (for incoming and outgoing data)
l
Chapter 10: Setting Up Communication to the Monitoring Portal
If grounded metal conduit are