Connecting to the Battery

Connecting to the Battery
To simplify the connection process it is advised to connect the battery to the inverter   b efore mounting 
the battery according to the manufacturer instructions.
Follow these guidelines: 
 
For easy access to battery connectors, it is recommended to connect the cables to the battery and 
l
to set all the battery DIP switches to their correct positions while the battery is still on the ground. 
The following procedure is recommended:
 a.  Connect all the wires to the battery connection panel
 b.  Mount the battery
 c.  Assemble the conduit between the battery and the inverter
 d.  Connect to the StorEdge Connection Unit
 
Measure the necessary length between the StorEdge Connection Unit and the battery for all cables. 
l
The maximum distance between the battery and the inverter is 35 ft/ 10m, when using 16AWG for 
battery thermal power and 24AWG for battery control.
 
Tie and wrap the cables   t o avoid pulling them out during mounting.
l
 
Be sure to adhere to all safety cautions and information in the battery documentation. 
l
 
The battery   c onnects to the DC side of the inverter. Since the inverter DC connections are on its left 
l
side, it is recommended to position the battery   t o the left of the inverter to simplify wiring.
NOTE
Per NEC requirements, if the battery is more than 5ft/ 1.5m away from the inverter, an additional
external DC switch ia required adjacent to the battery.
Prepare cables and connect as described in the following table (see Figure 19):
Recommended cable type
(min-max AWG)
DC
DC cable 10AWG (10-24 AWG),
600V insulated.
12V thermal power input
2-wire shielded twisted pair cable
16AWG (12-28AWG), 600V
insulated
30
StorEdge
Connection
Tesla battery
Unit
connection
connection
BAT DC +
DC+
terminal block
BAT DC-
DC-
terminal block
Battery
Thermal V-
THERMAL -
(black)
Battery
Thermal V+
THERMAL +
(red)
SolarEdge-StorEdge Installation Guide MAN-01-00262-1.0
Connection method
Insert a flat blade screwdriver into
o
the square opening at the top of the
terminal block and press to open
clamp mechanism.
Insert the wire into the round
o
opening and release the
screwdriver to spring back and
clamp the wire.
Push the lever to open the connection,
insert the wire and release the lever
when the wire is clamped.