3.21 HEAT PUMP DISABLING FUNCTION

No request will be met, excluding the safety functions.
To enable this function, please edit the following parameters:
Heat pump / Powers / HP power off = Yes
User / Disable HP = Yes
One can then choose whether to activate the disabling according to a schedule by setting time slots in the menu:
User / Start hourly HP disab.
User / End hourly HP disab.
or via an external contact that can be connected to the expansion kit.

3.22 POWER REDUCTION FUNCTION

To enable this function, please edit the following parameters:
User / Disable HP = Yes
Heat pump / Powers / HP power off = Reduct.
One can then choose whether to activate the reduction according to a schedule by setting time slots in the menu:
User / Start hourly HP disab.
User / End hourly HP disab.
or via an external contact that can be connected to the expansion kit.

3.23 DIVERTER VALVE MANAGEMENT (SUMMER / WINTER).

Valid only in combination with the Two Multifunction Relay Kit.
The two multi-function relay kit allows the potential-free contact of the outlet to be used to control a 3-way summer/winter valve (Pos. 18,
Fig. 27). Contact closure occurs in SUMMER mode.
To enable this function, it is necessary to adjust the parameter:
System definition / Multifunction relay 1 o Multifunction relay 2 o Multifunction relay 3 = 5

3.24 DIVERTER VALVE MANAGEMENT (DHW/SYSTEM) (OPTIONAL)

The two multi-function relay kit allows the potential-free contact of the outlet to be used to control a 3-way DHW/system valve (Pos. 18,
Fig. 27). Contact closure occurs in SYSTEM mode.
To enable this function, it is necessary to adjust the parameter:
System definition / Multifunction relay 1 o Multifunction relay 2 o Multifunction relay 3 = 6

3.25 HEAT PUMP CIRCULATOR FUNCTION

The operating mode of the heat pump circulator can be defined via the parameter:
Menu / Support / Heat pump / Pump
When set to Max Sp. the circulator will always run at the speed defined by the parameter Max pump speed; when set to Modul. the circu-
lator will run at a variable speed between the values defined by the parameters Max pump speed and Min pump speed with control logics
aimed at minimising consumption and guaranteeing the temperature delta between flow and return defined by the parameter Pump T
Delta.