The first served operating mode, in case of contemporaneity, is decided with the parameter:
Configuration / Priority
The DHW Mode can have a maximum duration, settable with the parameter
Configuration / Max time DHW
beyond which the alarm is signalled.
The heat pump can manage up to 3 distribution pumps.
To activate the correct number of distribution pumps, modify the parameter:
System definition / Number of zones
It is possible to customise the operation of each individual zone.
Each zone can be enabled for a single operating mode, modifying the parameter
Configuration / Enablings / Mode
The system request for each zone can be made from a room thermostat, which must be enabled in the menu
Configuration / Enablings / Enable room thermostat
In case a remote device is used to control the requests, it is necessary to modify the parameter
Configuration / Enablings / Enable remote contr.
If a dehumidifier is present, it is necessary to modify the parameter
Configuration / Enablings / Enable dehumidifiers
It can happen that the dehumidifier has problems with receiving a very high supply temperature. For this reason, dehumidifier ignition
can be prevented until the flow water drops below the level
Configuration / Enablings / Max dehum. temp.
Furthermore, if the setpoint calculated for the dehumidification is too high to carry out a request, the alarm is signalled and the dehu-
midifier is stopped. This value can be edited through the parameter:
Configuration / Enablings / Dehum. alarm set
In case a humidistat is used to control the dehumidification requests, it is necessary to modify the parameter
Configuration / Enablings / Enable humidistat
In the presence of a floor system, it is necessary to avoid the formation of condensate in the floor by enabling the use of the dew tempera-
ture calculation:
Configuration / Enablings / Enable dew point
It is possible to enable the flow temperature control via the thermoregulation with external probe, by modifying the parameter
Configuration / Enablings / Ext. probe modul.
To improve system efficiency in certain types of systems, it is possible to enable the flow temperature control by modulating with room
probe, by modifying the parameter
Configuration / Enablings / Room. probe modul.
The system flow temperature drops (it rises in case of cooling) when the room temperature approaches the room setpoint. Modulation
with room probe can only be enabled in the presence of a zone remote device.