Immergas MAGIS HERCULES PRO MINI 6 Instructions And Recommendations page 87

Hide thumbs Also See for MAGIS HERCULES PRO MINI 6:
Table of Contents

Advertisement

Menu item
Number of zones
Defines the number of zones present
Defines the main zone of the system in which the remote panel
Main zone
will be used
This defines the type of external probe enabled.
External probe (*)
- IU = indoor unit
- OU = outdoor unit.
External probe corr.
Correction of the external probe value
Photovoltaic function
Enables the operation combined with a photovoltaic system.
System supervision
Enabling connection to Dominus or System supervisor
Waiting time before activation of the system setpoint correc-
Activation time
tion
Time interval for the increase or decrease of 1°C of correction of
Increase time
the system setpoint
Max CH adjust
Max correction during central heating mode
Max Cool. adjust
Max correction during cooling mode.
0 = Disabled.
1 = Zone 3 in neutral air dehumidification contact.
2 = Zone 2 in neutral air dehumidification contact.
3 = Zone 1 in cooled air dehumidification contact.
Multifunction relay 1
4 = Zone 2 in cooled air dehumidification contact.
5 = Summer/Winter valve contact.
6 = DHW/System valve contact
7 = Recirculation pump contact.
0 = Disabled.
1 = Zone 3 in neutral air dehumidification contact.
2 = Zone 2 in neutral air dehumidification contact.
3 = Zone 1 in cooled air dehumidification contact.
Multifunction relay 2
4 = Zone 2 in cooled air dehumidification contact.
5 = Summer/Winter valve contact.
6 = DHW/system valve contact.
7 = Recirculation pump contact.
0 = Disabled.
1 = Zone 3 in neutral air dehumidification contact.
2 = Zone 2 in neutral air dehumidification contact.
3 = Zone 1 in cooled air dehumidification contact.
4 = Zone 2 in cooled air dehumidification contact.
Multifunction relay 3
5 = Summer/Winter valve contact.
6 = DHW/System valve contact
7 = Recirculation pump contact.
8 = Not used
9 = Zone 1 in neutral air dehumidification contact.
10 = Zone 1 in cooled air dehumidification contact.
(*) It is not possible to use the external probe IU (optional) when using DHW recirculation.
Menu / Support / System definition
Description
Range
Default
1-3
1
1-2-3
1
OU / IU
OU
-9 +9
0
Yes / No
No
No/Domin/
No
BMS
1 - 120
20
1 - 20
5
0 - 10
0
-10 - 0
0
0 - 7
0
0 - 7
0
0 - 10
0
Customised
value
87