Without the external probe it defines the maximum flow
temperature that can be set by the user. With the external probe
Max flow set
present it defines the maximum flow temperature correspond-
ing to operation with minimum external temperature
Without the external probe it defines the minimum flow
temperature that can be set by the user. With the external probe
Min flow set
present it defines the minimum flow temperature correspond-
ing to operation with maximum external temperature
With the external probe present it defines at what minimum
Min. outside temp.
external temperature the system must operate at the maximum
flow temperature
With the external probe present it defines at what maximum
Max. outside temp.
external temperature the system must operate at the minimum
flow temperature
Menu item
Without the external probe it defines the maximum flow that
can be set by the user. With the external probe present it defines
Max flow set
the maximum flow temperature corresponding to operation
with minimum external temperature
Without the external probe it defines the minimum flow that
can be set by the user. With the external probe present it defines
Min flow set
the minimum flow temperature corresponding to operation
with maximum external temperature
With the external probe present, it defines at what maximum
Min. outside temp.
external temperature the system must operate at the minimum
flow temperature
With the external probe present, it defines at what minimum
Max. outside temp.
external temperature the system must operate at the maximum
flow temperature
(*) if present.
Zones / Zone 2 (*) / Configuration / Thermoreg. CH
Description
Zones / Zone 2 (*) / Configuration / Thermoreg. Cool.
Description
Range
Default
20 ÷ 65 °C
45
20 ÷ 65 °C
25
-25 ÷ +15 °C
-5
-5 ÷ +45 °C
25
Range
Default
5 ÷ 25 °C
20
5 ÷ 25 °C
18
20 ÷ 45 °C
25
20 ÷ 45 °C
35