Heat pump disabling
It is possible to disable the heat pump operation for a certain time slot, by setting
User / Disable HP = Yes
and the start and end times of disabling.
Integration Disabling
The use of the integration electrical resistances can be permanently disabled by setting
User / Disable Integration = Yes
Automatic Vent Function
In the case of new systems and, in particular, for floor systems, it is very important that de-aeration is performed correctly.
The function consists of the cyclic activation of the pumps and the 3-way valve.
The function is activated by setting
User / Enable func. Deaeration = Yes
De-aeration lasts 9 hours and it can be interrupted by setting
User / Enable func. Deaeration = No
Screed Heater Function
The indoor unit is equipped with a function to perform the thermal shock on new radiant panel systems, as required by the applicable
standard.
Contact the manufacturer of the radiant panels for the thermal shock characteristics and its correct execution.
To be able to activate the function there must be no remote control connected, while in case of system divided into zones it must
be properly connected, both hydraulically and electrically.
The active zone pumps are those with ongoing requests, made via the room thermostat input.
The standard function lasts in total 7 days - 3 days at the lowest temperature set and 4 days at the highest temperature set (Fig. 33).
Duration can be changed by changing the value of the parameters
Screed heater / Min dwell time set
Screed heater / Max dwell time set
and the temperature gradients within the same menu.
The function is activated from the indoor unit in stand-by, by accessing the menu
Screed heater / Activation
At this point, "Screed heater underway" appears on the display.
In case of failure, the function is suspended and will resume when normal operating conditions are reset from the point where it was in-
terrupted.