Open the control panel connections compartment (Fig. 11).
To carry out electrical connections, all you have to do is open the connections compartment as follows.
1. Remove the cover and the aesthetic profile.
2. Disassemble the cover.
3. Loosen the screws (a).
4. Remove the cover (b) from the control panel (c).
At this point, you can access the terminal board.
Electrical connections to the control panel
The electrical connections available are:
• Photovoltaic system: connecting the product to a photovoltaic system enhances use of the outdoor unit when the photovoltaic panels
are operating.
• Dehumidifier zone 1.
• Summer/winter diverter.
• Multifunction relay.
• Zone 1 humidistat and thermostat.
• Zone 1 remote devices (Zone remote panel, Temperature/humidity probe, Dominus).
• External probe
• Heat pump disabling.
Make the various electrical connections according to your needs (Fig. 12).
Outdoor unit electrical connection
The indoor unit must be coupled to an outdoor unit by connecting terminals F1 and F2 as shown in the wiring diagram (Fig.13). The out-
door unit is powered at 230 V, regardless of the indoor unit.
Configure the parameter "HP Model" as indicated in the paragraph (Par. 3.9) according to the type of connected outdoor unit.