GENERAL

This manual describes the installation of a YORK YK
Mod "H" Centrifugal Chiller. This unit can be shipped
as a single factory assembled, piped, wired package,
requiring a minimum of field labor to make chilled
water connections, condenser water connections, re-
frigerant atmospheric relief connections, and electri-
cal power connections. Refrigerant and oil charges are
shipped separately unless optional condenser isolation
valves are ordered.
Chillers can also be shipped dismantled when required
by rigging conditions, but generally it is more econom-
ical to enlarge access openings to accommodate the
factory assembled unit. Chillers shipped dismantled
MUST be field assembled under the supervision of a
Johnson Controls representative, but otherwise instal-
lation is as described in this instruction.

FIELD ASSEMBLED UNITS ONLY

Use Unit - Installation Instructions (Form 160.76-N3)
in conjunction with this installation instruction. This in-
struction is furnished with all units that are assembled
in the field.
CONDENSER

FIGURE 1 - MODEL YK CHILLER

JOHNSON CONTROLS

SECTION 1 - INTRODUCTION

The services of a Johnson Controls representative will
be furnished to check the installation, supervise the
initial start-up and operation of all chillers installed
within the Continental United States.
COMPRESSOR
CONTROL
CENTER
The Johnson Controls Warranty may be
voided if the following restrictions are not
adhered to:
• Do not open valves or connections under any cir-
cumstances, as such action will result in loss of
the factory nitrogen charge.
• Do not dismantle or open the chiller for any rea-
son except under the supervision of a Johnson
Controls representative.
• When the units are shipped dismantled, notify the
nearest Johnson Controls office in ample time for
a Johnson Controls representative to supervise
rigging the unit to its operating position and the
assembly of components.
• Do not make final power supply connections to
the compressor motor or control center.
EVAPORATOR
1
VSD PANEL
LD15222
7