2
Connecting PV Strings
To minimize electromagnetic interference (EMI), make sure to
minimize the distance between the positive and negative DC cables
4
MAN-01-00XXX-1.0
Max distance between a combiner
box and any string: 150m / 492ft
Combiner Box
-
+
Turn off switches and check
string polarity. Verify 1±0.1V
per optimizer.
Example: 20 optimizers = ~20V
20V
Max distance between inverter
and combiner box: 700m / 2297ft
When connecting three or
more H1300 strings to a
combiner box, it is
recommended to use a 30A
fuse for each individual
string. However, be sure to
check local electrical codes
and regulations to
determine the proper fuse
sizing for your specific
installation.
Combiner Box