Figure 32 - Ten Fan Units Dimensions - Ylaa0170Se, Ylaa0156He, Ylaa0175He - York YLAA0041 Manual

Air-cooled scroll chiller
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
DIMENSIONS – YLAA0170SE, YLAA0156HE, YLAA0175HE
(OPTIONAL HEAT
RECOVERY UNIT)
3" VICTAULIC OUTLET
3" VICTAULIC INLET
140.8mm OR 288.0mm
[5.54"]-[11.34"] -DIMENTION VARIES BASED
ON CHILLER MODEL SELECTED
2242.1 [88.27]
FRAME WIDTH
2254.4 [88.76]
OVERALL WIDTH
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. Johnson Control's unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: Side to wall – 6 ft; rear to wall – 6 ft; control panel to end wall – 4 ft;
top – no obstructions allowed; distance between adjacent units – 10 ft. No more than one adjacent wall may be higher than the unit.
FIGURE 32 - TEN FAN UNITS DIMENSIONS – YLAA0170SE, YLAA0156HE, YLAA0175HE
JOHNSON CONTROLS
TEN FAN UNITS
1753.2
ORIGIN
[69.03]
194.6
[7.66]
588.3 [23.16]
1256.1 [49.45]
2061.5
[81.16]
3154.3
[124.18]
15.9mm [5/8"] DIA
MOUNTING HOLES (TYP.)
1839.5
1621.5
[72.42]
[63.84]
4" VICTAULIC INLET
4" VICTAULIC OUTLET
2002.8
[78.85]
5260.0
[207.08]
5848.3 [230.25]
FRAME LENGTH
5885.7 [231.72]
OVERALL LENGTH
SECTION 5 – TECHNICAL DATA
035-24059-012 REV-B
POWER ENTRY
330.2 [13.00] WIDE X 177.8 [7.00] HIGH
1177 [46.35]
CONTROL PANEL BOTTOM DETAIL
4" VICTAULIC
INLET
4" VICTAULIC
OUTLET
136.8 [5.38]
LD26942
97
5 5