York YLAA0041 Manual page 60

Air-cooled scroll chiller
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

SECTION 5 – TECHNICAL DATA
TABLE 11 - ELECTRICAL DATA WITHOUT PUMPS (CONT'D)
CHILLER
VOLTAGE
MODEL
CODE
156
170
175
200
230
60
MIN CKT.
AMPS
208
634
230
632
380
383
460
319
575
252
208
740
230
738
380
447
460
372
575
295
208
740
230
738
380
447
460
372
575
295
208
734
230
731
380
443
460
369
575
292
208
959
230
956
380
599
460
504
575
359
MIN DUAL
MIN N/F
ELEM
DISC SW
FUSE AND
MIN CB
800
700
800
700
600
400
400
350
400
300
1000
800
1000
800
600
500
600
400
400
350
1000
800
1000
800
600
500
600
400
400
350
1000
800
1000
800
600
500
600
400
400
300
1200
1000
1200
1000
600
600
600
600
600
400
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
MAX DUAL
ELEM
FUSE
MAX CB
700
700
400
350
300
800
800
500
400
350
800
800
500
400
350
800
800
500
400
300
1000
1000
600
600
400
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents