Electrical Data; Compressor Heaters; Table 7 - Micropanel Power Supply; Table 8 - Voltage Range - York YLAA0041 Manual

Air-cooled scroll chiller
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

SECTION 5 – TECHNICAL DATA

TABLE 7 - MICROPANEL POWER SUPPLY

UNIT VOLTAGE
UNIT
MODELS W/O
VOLTAGE
CONTROL
TRANS
-17
-28
MODELS W/
-40
CONTROL
-46
TRANS
-50
-58
A. Minimum #14 AWG, 75°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
It is possible that multiple sources of
power can be supplying the unit power
panel. To prevent serious injury or death,
the technician should verify that NO
LETHAL VOLTAGES are present inside
the panel AFTER disconnecting power,
before working on equipment.
Voltage Limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.

TABLE 8 - VOLTAGE RANGE

VOLTAGE CODE
-17
-28
-40
-46
-50
-58

COMPRESSOR HEATERS

Compressor heaters are standard. Smaller compres-
sors use 70 W heaters and larger compressors use 120
W heaters. If power is OFF more than two hours, the
crankcase heaters must be energized for 18 hours to 24
54

ELECTRICAL DATA

CONTROL
MCA
POWER
NOTE A
115-1-60/50
15 A
200-1-60
15 A
230-1-60
15 A
380-1-60
15 A
460-1-60
15 A
380/415-1-60
15 A
575-1-60
15 A
VOLTAGE RANGE
UNIT POWER
200/3/60
208/3/60
230-3-60
380-3-60
460-3-60
380/415-3-50
575-3-60
hours before restarting a compressor. This ensures that
liquid slugging and oil dilution does not damage the
compressors on start.
OVER CURRENT PROTECTION,
SEE NOTE B
MIN
MAX
10 A
15 A
10 A
15 A
10 A
15 A
10 A
15 A
10 A
15 A
10 A
15 A
10 A
15 A
The unit evaporator heater uses 120 VAC.
Disconnecting 120 VAC power from the
unit, at or below freezing temperatures,
can result in damage to the evaporator
and unit as a result of the chilled liquid
freezing.
MIN.
180
187
207
355
414
360
517
FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
NF DISC SW
30 A / 240 V
30 A / 240 V
30 A / 240 V
30 A / 480 V
30 A / 480 V
30 A / 415 V
30 A / 600 V
MAX.
220
228
253
415
506
440
633
JOHNSON CONTROLS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents