Table 35 - Data Logging To Flash - York YLAA0041 Manual

Air-cooled scroll chiller
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022

TABLE 35 - DATA LOGGING TO FLASH

DATA
HEADER
NUMBER
TEXT
1
Date
2
Time
3
Elapsed Time
4
LCHLT
5
RCHLT
6
LHLT
7
RHLT
8
Ambient Air
9
Active Cool Setp
10
Active Heat Setp
11
Evap Heater
12
Evap Pump
13
Evap Pump 2
14
Biv Ht Step
15
Drip Tray Htr
16
Mode Select
17
Lead System
18
Flow Switch
19
S1 Run Time
20
S1 Operating Code
21
S1 Fault Code
22
S1 Suct Press
23
S1 Act_Spc
24
S1 Dsch Press
25
S1 Suct Temp
26
S1 Sat Suct Temp
27
S1 Suct Sheat
28
S1 C1 Run
29
S1 C2 Run
30
S1 C3 Run
31
S1 LLSV
32
S1 Hot Gas
33
S1 Fan Stage
34
S1 Fan Speed
35
S1 Comp Seq
36
S1 CIR Temp
37
S1 Dsch Sheat
38
S1 Sheat Setp
39
S1 Dsch Temp
40
S1 EEV Cmd
41
S1 EEV PWM
JOHNSON CONTROLS
UNIT
FORMAT
x/x/xxxx
Date
x:x:x
Time (24 Hour Format)
s
x
Elapsed time (seconds since data logging started)
°F
x.x
Leaving Chilled Liquid Temperature
°F
x.x
Return Chilled Liquid Temperature
°F
x.x
Leaving Hot Liquid Temperature (YCWL)
°F
x.x
Return Hot Liquid Temperature (YCWL)
°F
x.x
Ambient Air Temperature (N/A YCWL)
°F
x.x
Active Cooling Setpoint
°F
x.x
Active Heating Setpoint
x
Evaporator Heater Status
x
Evaporator Pump Contact Status
x
Evaporator Pump 2 Contact Status (Hydro Kit 2)
x
Bivalent Heat Step (YLAE)
x
Drip Tray Heater (YLPA)
x
Mode Select (YCWL) (0=Chiller, 1=Heatpump)
x
Lead System (0=System1, 1=System2)
x
Flow Switch Status
s
x
Sys 1 Run Time
x
Sys 1 Operational Code
x
Sys 1 Fault Code
psig
x.x
Sys 1 Suction Pressure
psig
x.x
Sys 1 Actual Suction Pressure Cutout
psig
x.x
Sys 1 Discharge Pressure
°F
x.x
Sys 1 Suction Temperature
°F
x.x
Sys 1 Saturated Suction Temperature
°F
x.x
Sys 1 Suction Superheat
x
Sys 1 Compressor 1 Run Status
x
Sys 1 Compressor 2 Run Status
x
Sys 1 Compressor 3 Run Status
x
Sys 1 Liquid Line Solenoid Valve Status
x
Sys 1 Hot Gas Bypass Solenoid Valve Status
x
Sys 1 Condenser Fan Stage
%
x
Sys 1 VSD Fan Speed (VSD Fans)
x
Sys 1 Programmed Compressor Sequence (1=C1, 2=C2, 3=C3)
°F
x.x
Sys 1 Cooler Inlet Refrig. Temp (R-407c)
°F
x.x
Sys 1 Discharge Superheat (discharge temperature sensors
enabled)
°F
x.x
Sys 1 Superheat Setpoint
Sys 1 Discharge Temperature (discharge temperature sensors
°F
x.x
enabled)
x
Sys 1 EEV Command (0 – 100%) 031-02755-001, -003
%
x.x
Sys 1 EEV Command (0.0 – 100.0%) 031-02755-004
%
x
Sys 1 EEV PWM (0 – 100%) 031-02755-001, -003
SECTION 9 – SERVICE AND TROUBLESHOOTING
DATA
VALUE DESCRIPTION
9
193

Hide quick links: