Leaving Chilled Liquid Control Override To Reduce Cycling; Figure 47 - Setpoint Adjust; Table 24 - Sample Compressor Staging For Return Water Control - York YLAA0041 Manual

Air-cooled scroll chiller
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022

TABLE 24 - SAMPLE COMPRESSOR STAGING FOR RETURN WATER CONTROL

# OF COMP ON
45°F
RWT
(7.2°C)
*Unloading only
LEAVING CHILLED LIQUID CONTROL
OVERRIDE TO REDUCE CYCLING
To avoid compressor cycling the microprocessor ad-
justs the setpoint upward temporarily. The last run time
of the system is saved. If the last run time was greater
than 5 minutes, do not take any action. If the last run
time for the lead system was less than 5 minutes, the
microprocessor increases the setpoint high limit ac-
cording to the chart at right, with a maximum value
allowed of 50°F. See Figure 47.
If adding the setpoint adjust value to the setpoint high
limit causes the setpoint high limit to be greater than
50°F, the setpoint high limit is set to 50°F and the dif-
ference is added to the setpoint low limit.
When a system runs for greater than 5 minutes, the set-
point adjust sets back to 0. This occurs while the sys-
tem is still running.
JOHNSON CONTROLS
4 COMPRESSOR
COOLING SETPOINT = 45 °F (7.2 °C) RANGE = 10 °F (5.6 °C)
0
* 1+HG
46.25°F
(7.9°C)
1
2
47.5°F
50.0°F
(8.6°C)
(10.0°C)
6
5
4
3
2
1
0
0
1
2
LAST RUN TIME OF LEAD SYSTEM (MINUTES)

FIGURE 47 - SETPOINT ADJUST

SECTION 8 – UNIT OPERATION
3
4
52.5°F
55.0°F
(11.4°C)
(12.8°C)
3
4
5
6
LD11415
177
8