FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
Control Center
All controls are contained in a NEMA 3R/12 cabinet
with hinged outer door and includes a Liquid Crystal
Display with Light Emitting Diode backlighting for
outdoor viewing:
• Two display lines
• Twenty characters per line
Display/Print Keys
• Color coded 12-button non-tactile keypad with sec-
tions for display and print of typical information:
• Chilled liquid temperatures
• Ambient temperature
• System pressures (each circuit)
• Operating hours and starts (each compressor)
• Print calls up to the liquid crystal display
• Operating data for the systems
• History of fault shutdown data for up to the last
six fault shutdown conditions.
• An RS-232 port, in conjunction with this press-to-
print button, is provided to permit the capability
of hard copy print-outs via a separate printer (by
others).
Entry Keys
This section is used to enter setpoints or modify system
values.
Setpoints Keys
Updating can be performed to:
• Chilled liquid temperature setpoint and range
• Remote reset temperature range
• Set daily schedule/holiday for start/stop
• Manual override for servicing
• Low and high ambient cutouts
• Number of compressors
• Low liquid temperature cutout
• Low suction pressure cutout
• High discharge pressure cutout
• Anti-recycle timer (compressor start cycle time)
• Anti-coincident timer (delay compressor starts)
JOHNSON CONTROLS
SECTION 2 – PRODUCT DESCRIPTION
Unit Keys
This section is used to:
• Set time
• Set unit options
Oper Data Key
The microprocessor control center is capable of dis-
playing the following:
• Return and leaving liquid temperature
• Low leaving liquid temperature cutout setting
• Low ambient temperature cutout setting
• Outdoor air temperature
• English or Metric data
• Suction pressure cutout setting
• Each system suction pressure
• Discharge pressure (optional)
• Liquid Temperature Reset via a Johnson Controls
ISN DDC or Building Automation System (by
others) via a 4 mA to 20 mA or 0 VDC to 10 VDC
input
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition
• Compressor run status
• No cooling load condition
• Day, date and time
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag control
• Lead system definition
• Compressor starts and operating hours
• (each compressor)
• Status of hot gas valves, evaporator heater
and fan operation
• Run permissive status
• Number of compressors running
• Liquid solenoid valve status
• Load and unload timer status
• Water pump status
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and
two steps of demand load limiting from an external
building automation system. Unit alarm contacts are
standard.