York YLAA0041 Manual page 137

Air-cooled scroll chiller
Hide thumbs Also See for YLAA0041:
Table of Contents

Advertisement

FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
COOLING RANGE
42.0 +/- 2.0 DEGF
HEATING RANGE 122.0 +/- 2.0 DEGF
SYS 1 SETPOINT
SYS 2 SETPOINT
REMOTE SETPOINT
AMBIENT AIR TEMP
LEAD SYSTEM
EVAPORATOR PUMP
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
LAST DEFROST SYS X DURATION XXXS
TIME TO SYS X DEFROST
BIVALENT DELAY REMAINING XX MIN
UNIT
XXX.X AMPS
SOFTWARE VERSION
SYSTEM 1 DATA
COMP STATUS
1=OFF 2=OFF 3=OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
TIME YYYYYYY 0- 0- 0- 0 D-H-M-S
LAST STATE
SUCTION PRESSURE
DISCHARGE PRESSURE
SUCTION TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
COOLER INLET REFRIG
DEFROST TEMPERATURE
LIQUID LINE SOLENOID
MODE SOLENOID
HOT GAS BYPASS VALVE
CONDENSER FAN STAGE
EEV OUTPUT
SYSTEM
XXX.X AMPS X.X VOLTS
SYSTEM 2 DATA
COMP STATUS
1=ON, 2=OFF, 3=ON
RUN TIME
0-0-1-46 D-H-M-S
TIME YYYYYYY
0-0-0-0 D-H-M-S
LAST STATE
SUCTION PRESSURE
DISCHARGE PRESSURE
SUCTION TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
COOLER INLET REFRIG
DEFROST TEMPERATURE
LIQUID LINE SOLENOID
MODE SOLENOID
CONDENSER FAN STAGE
EEV OUTPUT
SYSTEM
XXX.X AMPS
DAILY SCHEDULE
S M T W T F S
SUN START=00:00AM STOP=00:00AM
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
JOHNSON CONTROLS
70 +/- 3 PSIG
70 +/- 3 PSIG
44.0 DEGF
74.8 DEGF
SYS 2
ON
OFF
NONE
XX MIN
X.X VOLTS
C.M02.13.00
YYYYYYY
105 PSIG
315 PSIG
46.0 DEGF
34.0 DEGF
12.0 DEGF
31.6 DEGF
52.8 DEGF
OFF
OFF
OFF
OFF
0.0 %
YYYYYYY
110 PSIG
320 PSIG
49.3 DEGF
36.0 DEGF
13.3 DEGF
31.6 DEGF
52.8 DEGF
ON
ON
3
63.2%
X.X VOLTS
*=HOLIDAY
See Optional Printer Installation on page
195 for Printer Installation information.
History Printout
Pressing the PRINT key and then the HISTORY key
allows the operator to obtain a printout of information
relating to the last 9 Safety Shutdowns which occurred.
The information is stored at the instant of the fault, re-
gardless of whether the fault caused a lockout to occur.
The information is also not affected by power failures
(long-term internal memory battery backup is built into
the circuit board) or manual resetting of a fault lock-
out.
When the HISTORY key is pressed, a printout is trans-
mitted of all system operating conditions which were
stored at the "instant the fault occurred" for each of the
9 Safety Shutdowns buffers. The printout will begin
with the most recent fault which occurred. The most
recent fault will always be stored as Safety Shutdown
No. 1. identically formatted fault information will then
be printed for the remaining safety shutdowns.
Information contained in the Safety Shutdown buffers
is very important when attempting to troubleshoot a
system problem. This data reflects the system condi-
tions at the instant the fault occurred and often reveals
other system conditions which actually caused the
safety threshold to be exceeded.
The history printout is similar to the operational data
printout shown in the previous section. The differences
are in the header and the schedule information. The
daily schedule is not printed in a history print.
One example history buffer printout is shown follow-
ing. The data part of the printout will be exactly the
same as the operational data print so it is not repeated
here. The difference is that the Daily Schedule is not
printed in the history print and the header will be as
follows.
YORK INTERNATIONAL CORPORATION
MILLENNIUM LIQUID CHILLER
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @ 3:56PM
SYS 1
HIGH DSCH PRESS SHUTDOWN
SYS 2
SECTION 7 – UNIT CONTROLS
29 SEP 07
NO FAULTS
137
7