Air-Cooled Scroll Chiller Installation, Operation, Supersedes: 150.72-ICOM6 (221) Form 150.72-ICOM6 (822) Maintenance 035-23572-100 YLAA0041 – YLAA0230 Air-Cooled Scroll Chillers With Brazed Plate Heat Exchanger Style B (60 HZ) 4–12 Fan 40 ton to 230 ton 140 kW to 800 kW...
Page 2
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or During rigging, installation, operation, maintenance, death to themselves and people at the site. or service, individuals may be exposed to certain com- This document is intended for use by owner-authorized ponents or conditions including, but not limited to:...
Page 3
Planned Service Agreement that leverages real time and generalized conditions. In lieu of the traditional and historical data, delivering performance reporting, maintenance program, a Johnson Controls YORK corrective actions required and data enabled guidance Conditioned Based Maintenance (CBM) program can for optimal operation and lifecycle assurance.
Page 4
17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60 S = STANDARD EFFICIENCY H = HIGH EFFICIENCY FOUR DIGIT UNIT NUMBER A = DESIGN SERIES A = AIR COOLED YL = YORK CHILLER JOHNSON CONTROLS...
Single-Point Supply Connection – Terminal Block, Non-Fused Disconnect Switch or Circuit Breaker ......................41 SECTION 5 – TECHNICAL DATA ........................47 Physical Data YLAA0041 – YLAA0230 60 Hz ....................50 Electrical Data ..............................54 Compressor Heaters ............................54 Electrical Notes .............................. 65 Weight Distribution and Isolator Mounting Positions ..................
Page 6
Return Chilled Liquid System Lead/Lag and Compressor Sequencing ............178 Anti-Recycle Timer ............................178 Anti-Coincidence Timer ..........................178 Evaporator Pump Control and YORK Hydro Kit Pump Control ..............178 Evaporator Heater Control ........................... 179 Pumpdown Control ............................179 Standard Condenser Fan Control ........................ 179 VSD Fan ...............................
Page 7
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 TABLE OF CONTENTS (CONT’D) SECTION 9 – SERVICE AND TROUBLESHOOTING ..................185 Clearing History Buffers..........................185 Resetting System Lockout Faults ......................... 185 Service Mode ............................... 185 Service Mode – Outputs ..........................185 Service Mode – Chiller Configuration ......................186 Service Mode –...
Page 8
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 LIST OF FIGURES FIGURE 1 - Compressor Enclosure for YLAA0041HE ...................16 FIGURE 2 - Unit Components (Front) ........................21 FIGURE 3 - Unit Components (Side) ........................22 FIGURE 4 - Power Panel Components ........................23 FIGURE 5 - Power Panel / Control Components ....................24 FIGURE 6 - Process and Instrumentation Diagram ....................31 FIGURE 7 - Rigging and Lifting Label ........................33 FIGURE 8 - Unit Rigging/Lifting ..........................35...
Page 9
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 LIST OF TABLES TABLE 1 - Canadian Registration Numbers ......................16 TABLE 2 - Complete Pin Number Description ......................25 TABLE 3 - Chemical Specification of Water ......................43 TABLE 4 - Temperatures and Flows ........................47 TABLE 5 - Ethylene and Propylene Glycol Correction Factors ................49 TABLE 6 - Physical Data (English) 60 Hz ......................50 TABLE 7 - Micropanel Power Supply ........................54 TABLE 8 - Voltage Range ............................54...
Page 10
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY INTRODUCTION serial number information is printed on the unit identi- YORK YLAA chillers are manufactured to the highest fication plate. design and construction standards to ensure high per- formance, reliability, and adaptability to all types of air The unit warranty will be void if any modification to conditioning installations.
FORM 150.72-ICOM6 SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 08/03/2022 • ASHRAE 90.1 - Energy Efficiency compliance. Structural Support Structural support of the unit must be provided as in- • Conform to Intertek Testing Services, formerly dicated in these instructions. Failure to provide proper ETL, for construction of chillers and provide support may result in injury to the operator, or damage ETL/cETL listing label.
Page 13
FORM 150.72-ICOM6 SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 08/03/2022 Rotating Parts High Temperature and Pressure Cleaning Fan guards must be fitted at all times and not removed High temperature and pressure cleaning methods (for unless the power supply has been isolated. If ductwork example steam cleaning) should not be used on any part is to be fitted, requiring the wire fan guards to be re- of the pressure system as this may cause operation of...
Page 14
FORM 150.72-ICOM6 ISSUE DATE: 12/18/2020 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
ISSUE DATE: 08/03/2022 SECTION 2 – PRODUCT DESCRIPTION INTRODUCTION GENERAL SYSTEM DESCRIPTION YORK YLAA Air-Cooled Scroll Chillers provide Compressors chilled water for all air conditioning applications us- The chiller has suction-gas cooled, hermetic, scroll ing central station air handling or terminal units. They compressors.
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 label or marking is not provided on the evaporator. Ac- COMPRESSOR cording to the Canadian Standards Association’s Boil- ENCLOSURE er, Pressure Vessel, and Pressure Piping Code B-51 (2009 version), a product registered as a category “H” fitting does not require a label or marking displaying the CRN.
Page 17
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 Control Center Unit Keys All controls are contained in a NEMA 3R/12 cabinet This section is used to: with hinged outer door and includes a Liquid Crystal • Set time Display with Light Emitting Diode backlighting for •...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 The operating program is stored in non-volatile memo- Single-Point Supply Terminal Block ry battery backed RAM to eliminate chiller failure due Includes enclosure, terminal-block, and interconnect- to AC powered failure/battery discharge. Programmed ing wiring to the compressors.
Page 19
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 Compressor, Piping, Evaporator Options (60°C) are possible. Low Temperature Glycol Hydro-Kit Replaces standard Thermostatic Expansion Valves Factory installed Hydro-Kit suitable for water and gly- with Electronic Expansion Valves to achieve leaving col systems with up to 35% glycol at leaving tempera- glycol temperatures as low as 10°F (-12°C).
Page 20
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 • Louvered Panels (Full Unit) - Louvered panels • Compressor Acoustic Sound Blanket - Each surround the front, back, and sides of the unit. compressor is individually enclosed by an acous- tic sound blanket.
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 POWER POWER PANEL PANEL ITEM DESCRIPTION Fan assemblies MCHX condenser Control panel Compressors Receiver included with optional heat recovery condenser Filter driers FIGURE 2 - UNIT COMPONENTS (FRONT) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 ITEM DESCRIPTION Fan deck MCHX condenser Coil headers Control and power panels Compressors Brazed plate evaporator Formed steel base rails Hydro-kit pumps and motors (optional) FIGURE 3 - UNIT COMPONENTS (SIDE) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 LD13248 ITEM DESCRIPTION Fan contactor Fan fuses Control relay Microcomputer control center Display Keypad XTBC1 Microboard XTCB2 XTBF2 Compressor contactors Compressor overloads FIGURE 5 - POWER PANEL / CONTROL COMPONENTS JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 PRODUCT IDENTIFICATION NUMBER (PIN) TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION MODEL Model (PIN 1-4) YLAA 0041 0041 0048 0048 0058 0058 0065 0065 0070 0070 0080...
Page 26
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION No Control Transformer Required Cntrl Transformer TRANS Control Transformer Required (PIN 18) Special Control Transformer Required No Power Capacitor required Power Factor Capacitor Power Capacitor required...
Page 27
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION No Hot Gas Bypass required Hot Gas Bypass HGBP Hot Gas Bypass required - 1 circuit (PIN 33) Special Hot Gas Bypass required GAUGE...
Page 28
Base & Witness Documents Special Quote Standard York/JCI Branding Quantech Branding PIN 51 PIN 51 York/JCI Branding with Quantech bag SASO Compliant Label Special Quote Standard Low Sound Fan Required Ultra Quiet Fans Required High Air Flow Fan Requied Standard Low Sound Fan with VSD Required...
Page 29
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION No Isolators required 1 in. Deflection Isolators required Vibration Isolators ISOL Neoprene Isolators required (PIN 54) 2 in.
Page 30
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 08/03/2022 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION No Pump Pump Kit A Pump Kit B Pump Kit C Pump Kit D Pump Kit E Pump Kit F Pump Kit G Pump Kit H...
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 SECTION 3 – HANDLING AND STORAGE LD18119 FIGURE 7 - RIGGING AND LIFTING LABEL Read carefully the rigging warning label Rigging and lifting should only be done by on the chiller packaging. a professional rigger in accordance with a written rigging and lifting plan.
FORM 150.72-ICOM6 SECTION 3 – HANDLING AND STORAGE ISSUE DATE: 08/03/2022 DELIVERY AND STORAGE INSPECTION To ensure consistent quality and maximum reliability, Remove any transit packing and inspect the unit to en- all units are tested and inspected before leaving the fac- sure that all components have been delivered and that tory.
FORM 150.72-ICOM6 SECTION 3 – HANDLING AND STORAGE ISSUE DATE: 08/03/2022 LD18121 LD18120 4 - 6 Fan Units 8 Fan Units LD27282 10 Fan Units LD27283 12 Fan Units FIGURE 8 - UNIT RIGGING/LIFTING JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 3 – HANDLING AND STORAGE ISSUE DATE: 08/03/2022 LIFTING WEIGHTS LIFTING USING SHACKLES See the unit nameplate for unit shipping weight. Note Insert the shackles into the respective holes in the base that weight may vary depending on unit configuration frame and secure from the inside.
HP cutout settings, weight of the equipment. See Physical Data YLAA0041 design working pressures, and ventilation – YLAA0230 60 Hz on page 50 for operating weight.
Hand stop valves should be installed in all lines to fa- up during low ambient periods. cilitate servicing. • A chilled water flow switch, (either by YORK Piping to the inlet and outlet connections of the chiller or others) MUST be installed in the leaving wa- should include high-pressure rubber hose or piping ter piping of the cooler.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 08/03/2022 When ducting is to be fitted to the fan discharge it is PIPEWORK ARRANGEMENT recommended that the duct should be the same cross- The following are suggested pipework arrangements sectional area as the fan outlet and straight for at least for single unit installations, for multiple unit installa- 3 ft (1 m) to obtain static regain from the fan.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 08/03/2022 aluminum to copper. This transition should be done in Alarm Status Contacts an external box separate to the power panel. Copper Normally-open contacts are available for each re- conductors can then be run from the box to the chiller. frigerant system.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 08/03/2022 Specification of Water • Prevent particles such as silt, pipe slag, and bio- • Back flushing is an ideal method to clear out logical matter from entering the unit to prevent the blockage.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 08/03/2022 Thermal Dispersion Flow Switch: 1. Thermal Dispersion Flow Switch Operating Principle PIN NUMBERS The operating principle of the thermal dispersion flow switch is based on the calorimetric princi- ple. It uses the cooling effect of a flowing fluid to monitor the flow rate.
Page 45
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 08/03/2022 Generally, the thermal dispersion flow switch is shipped with the unit as a loose part. To mount the IFM thermal dispersion switch, use the following guidelines: • Use a pipe coupling to mount the thermal disper- •...
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 08/03/2022 USER CONTROL WIRING OUTPUTS INTERNAL WIRING TO EVAPORATOR HEATER INTERNAL WIRING TO HOT GAS SOLENOID VALVE SYSTEM 2 ALARM DRY CONTACTS (OPEN = ALARM) SYSTEM 1 ALARM DRY CONTACTS (OPEN = ALARM) SYSTEM 2 RUN DRY CONTACTS (CLOSE = RUN) SYSTEM 1 RUN DRY CONTACTS (CLOSE = RUN) EVAPORATOR PUMP DRY CONTACTS (CLOSE = RUN...
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 SECTION 5 – TECHNICAL DATA OPERATIONAL LIMITATIONS TABLE 4 - TEMPERATURES AND FLOWS TEMPERATURE, °F (°C) WATER FLOW, GPM (L/S) AIR ON CONDENSER, °F (°C) UNIT DESIGNATION MINIMUM MAXIMUM NOMINAL MINIMUM MAXIMUM MINIMUM MAXIMUM STANDARD EFFICIENCY YLAA0070SE 40 (4.4) 55 (12.8)
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 ELECTRICAL DATA TABLE 7 - MICROPANEL POWER SUPPLY OVER CURRENT PROTECTION, CONTROL UNIT VOLTAGE SEE NOTE B POWER NF DISC SW NOTE A UNIT MODELS W/O VOLTAGE 115-1-60/50 CONTROL 15 A 10 A 15 A 30 A / 240 V...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 TABLE 11 - ELECTRICAL DATA WITHOUT PUMPS MIN DUAL MAX DUAL CHILLER VOLTAGE MIN CKT. MIN N/F ELEM ELEM MODEL CODE AMPS DISC SW FUSE AND FUSE MIN CB MAX CB JOHNSON CONTROLS...
Page 58
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 TABLE 11 - ELECTRICAL DATA WITHOUT PUMPS (CONT’D) MIN DUAL MAX DUAL CHILLER VOLTAGE MIN CKT. MIN N/F ELEM ELEM MODEL CODE AMPS DISC SW FUSE AND FUSE MIN CB MAX CB JOHNSON CONTROLS...
Page 60
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 TABLE 11 - ELECTRICAL DATA WITHOUT PUMPS (CONT’D) MIN DUAL MAX DUAL CHILLER VOLTAGE MIN CKT. MIN N/F ELEM ELEM MODEL CODE AMPS DISC SW FUSE AND FUSE MIN CB MAX CB 1000 1000...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 ELECTRICAL NOTES the rated load amps for all other loads included in NOTES 1. Minimum Circuit Ampacity (MCA) is based on the circuit. Otherwise, HACR-type circuit breakers 125% of the rated load amps for the largest mo- must be used.
Page 66
HEATER RELAY STANDARD YORK ACCESSORIES COMPRESSOR CONTACTOR WIRING AND ITEMS SHOWN THUS ARE - KM (INCLUDING COIL SUPPRESSOR) NOT SUPPLIED BY YORK - KCR CONTROL RELAY ITEMS THUS ENCLOSED FORM A COMPONENTS OR SETS OF PUMP CONTACTOR PART - KP...
Page 67
Field wiring must be in accordance with the relevant electrical code and all other applicable codes and specifications. All sources of supply shown on this diagram must be taken from one main isolator, not shown or supplied by YORK. Green and yellow wire is used for earth, multi-colored cable used for low voltage. Red wire used for AC Control, blue wire for neutral, black wire for AC and DC power.
Page 68
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 ELECTRICAL NOTES AND LEGEND (CONT’D) Fitted on units with single phase motors only. Fitted on units with low ambient option only. Only fitted on units with an acoustic kit. Only fitted on heat recovery units. Only fitted on condensing units.
Page 69
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 CONNECTION - EEV OPTION 035-21499-105 Rev C =1-EEVC INPUT CONFIGURATION 0-10V J15-3 P15 TO MICROBOARD STEP-1 J15-7 STEP-2 STEP-3 POLARITY DIRECTION RESPONSE TIME PULSE PER SECOND 200pps VALVE OPERATION TO SYSTEM #1 EEV 24V+ 24V- FROM TRANSFORMER -1T...
Page 83
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 FOUR FAN UNITS DIMENSIONS – YLAA0070SE, YLAA0080SE, YLAA0089SE 1678 [66.1] 1117 [44.0] 035-24059-002 REV-E POWER ENTRY 330.2 [13.00] WIDE X 177.8 [7.00] HIGH (190mm x 120mm EUROPEAN BUILD) 1177 [46.4] (1298mm EUROPEAN BUILD) CONTROL PANEL BOTTOM DETAIL OPTIONAL...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 FIVE FAN UNITS DIMENSIONS – YLAA0100SE 2795 [110.0] 035-24059-004 REV-E 1678 [66.1] 561 [22.1] POWER ENTRY 330.2 [13.00] WIDE X 177.8 [7.00] HIGH (190mm x 120mm EUROPEAN BUILD) 1177 [46.4] 1298mm EUROPEAN BUILD CONTROL PANEL BOTTOM DETAIL OPTIONAL...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 SIX FAN UNITS DIMENSIONS – YLAA0092HE, YLA0101HE, YLAA0115SE, YLAA0120SE 2795 [110.0] 1678 [66.1] 035-24059-006 REV E 561 [22.1] POWER ENTRY 330.2 [13.00] WIDE X 177.8 [7.00] HIGH (190mm x 120mm EUROPEAN BUILD) 1177 [46.4] 1298mm EUROPEAN BUILD CONTROL PANEL BOTTOM DETAIL...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 TEN FAN UNITS DIMENSIONS – YLAA0170SE, YLAA0156HE, YLAA0175HE 15.9mm [5/8”] DIA MOUNTING HOLES (TYP.) 035-24059-012 REV-B POWER ENTRY 330.2 [13.00] WIDE X 177.8 [7.00] HIGH 1177 [46.35] CONTROL PANEL BOTTOM DETAIL 1753.2 1839.5 1621.5...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 WEIGHT DISTRIBUTION AND ISOLATOR Whenever the isolator option is ordered, the isolators MOUNTING POSITIONS will be shipped loose with the chiller. Packed with the isolators and also in the control panel informa- General tion packet is a drawing and table specifically for each Weights of specific chiller models vary significantly as...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 CLEARANCES See Figure 35 below for minimum clearances for all YLAA units. (2 m) (1.3 m) NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit. 3.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 ISOLATOR LOCATIONS FOUR FAN ISOLATOR LOCATIONS YLAA0041HE, YLAA0048HE, YLAA0058HE, YLAA0065HE, YLAA0081HE, YLAA0082HE LD18078 FOUR FAN ISOLATOR LOCATIONS YLAA0070SE, YLAA0080SE, YLAA0089SE LD18079 All dimensions are inches unless otherwise specified. JOHNSON CONTROLS...
Page 102
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 FIVE and SIX FAN ISOLATOR LOCATIONS YLAA0100SE, YLAA0120SE, YLAA0092HE, YLAA0101HE LD18080 EIGHT FAN ISOLATOR LOCATIONS YLAA0136SE, YLAA0155SE, YLAA0139HE, YLAA0142HE LD18081 All dimensions are inches unless otherwise specified. JOHNSON CONTROLS...
Page 103
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 TEN FAN ISOLATOR LOCATIONS YLAA0170SE, YLAA0156HE, YLAA0175HE LD18082 TWELVE FAN ISOLATOR LOCATIONS YLAA0200HE, YLAA0230HE VIEW LD21040 All dimensions are inches unless otherwise specified. JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 ISOLATOR INFORMATION 1 in. Deflection Spring Isolator Cross-reference 5/8" Ø1/2" H" C" T" B" L" D" W" LD13759A MOUNT DIMENSION DATA (IN.) TYPE TYPE A 7 3/4 6 1/2 4 3/4 5 5/8 TYPE B 10 1/2...
Page 105
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 1 IN. DEFLECTION SPRING ISOLATORS INSTALLATION INSTRUCTIONS 1. Read instructions in their entirety before begin- 6. The adjustment process can only begin after the ning installation. equipment or machine is at its full operating weight.
Page 107
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 2 IN. DEFLECTION ISOLATOR INSTALLATION AND ADJUSTMENT 1. Read instructions in their entirety before begin- equipment or bracket to the top plate (“A”) of iso- ning installation. lator with a minimum of 3/8 fillet welds 2 in. long at 3 in.
Page 108
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 NEOPRENE ISOLATOR CROSS-REFERENCE MOLDED DURULENE ø D THRU TYP 2 PLACES LD13760A 1. All dimensions are inches, interpreted per ANSI 4. AL = Mounting hole center to center spacing. Notes: Y14.
Page 109
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 08/03/2022 INSTALLATION OF NEOPRENE VIBRATION ISOLATORS 1. Read instructions in their entirety before begin- 4. Bolt or anchor all isolators to supporting structure ning installation. utilizing base hrough holes (“B”). 2. Isolators are shipped fully assembled and are to be 5.
Page 110
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 SECTION 6 – COMMISSIONING Commissioning of this unit should only Charging after vacuuming - Charge 10% be carried out by Johnson Controls Au- of the specified amount of refrigerant into thorized personnel. the evaporator. Otherwise, the compressor is in risk when it starts.
Page 112
Ensure that the leaving liquid temperature sensor is coated with heat conductive compound (Part No. 013- For Copeland compressors, use YORK V 00890-000) and is inserted to the bottom of the water oil, YORK P/N 011-00949-000. outlet sensor well in the cooler. This sensor also pro-...
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 JUMP INPUT LOCATION SIGNAL 0–10 V DIP SWITCH ALL OTHER YLAA0230 NUMBER CHILLERS DIP SWITCH NUMBER CHILLERS LD23530 FIGURE 36 - EEV IB-G INTERFACE BOARD Switch Settings Flow rates and pressure drops must be within the limits Ensure the chiller OFF/ON UNIT switch at the bottom given in SECTION 5 –...
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 COMMISSIONING THE PUMP VFD Sporlan EEV Interface Board Verify the jumper and dip switch settings, Figure 36 1. Put pump in HAND mode. on page 113, during a chiller start-up for YLAA and YCWL chillers with Sporlan Electronic Expansion Valves.
Page 115
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 Programming the Drive Instructions to access Service Mode are located on the chiller control panel. 1. To enable Service Mode, set the unit rocker switch to OFF. LD18421 2. Press the Program key. 3.
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 GROUP NAVIGATION PARAMETER STRUCTURE LD29434 FIGURE 37 - DRIVE DISPLAY Leave all other settings not listed in the following table in their default values. TABLE 13 - DRIVE PROGRAMMING PARAMETERS PARAMETER CODE DESCRIPTION SETTING 9902...
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 Setting the Adjustable Breaker The Maximum Over Current Protection (MOCP) for For a 200 A trip setting, set switches 0.08 and 0.32 each chiller is provided on the nameplate. The l1 trip in the up position.
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 DETERMINING PROPER OIL LEVELS The following charts list the proper oil levels in tandem and trio compressor manifold sets. TANDEM COMPRESSOR COMPRESSOR OIL LEVEL STATUS 1/8 to full SG Bottom of SG Bottom of SG 1/8 to full SG 1/8 to full SG...
Page 119
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 YLAA Supersedes 150.72-CL1 (320) INSTALLATION CHECKLIST Form 150.72-CL1 (1220) START-UP CHECKLIST CUSTOMER: ____________________________________ JOB NAME: ____________________________________ ADDRESS: _____________________________________ LOCATION: ____________________________________ PHONE: ________________________________________ CUSTOMER ORDER NO: _________________________ JCI TEL NO: _____________________ JCI ORDER NO: __________________ JCI CONTRACT NO: ______________ CHILLER MODEL NO: ____________________________ UNIT SERIAL NO: _______________________________...
Page 120
Remote Temperature Reset discharge service valves ..........External Evaporator Pump 7. Place the Unit Switch in the control panel to the ON YORK Hydro Kit Pump position ................ Pump Selection NOTE: The chilled liquid setpoint may need to be Data Log to Flashcard Enabled temporarily lowered to ensure all compressors cycle ON.
Page 121
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 08/03/2022 A. CHECKING SUPERHEAT AND SUBCOOLING The subcooling temperature of each system can be calcu- Example: lated by recording the temperature of the liquid line at the Suction temp. = 46°F outlet of the condenser and subtracting it from the liquid minus suction press.
Page 122
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
LD13283 INTRODUCTION IPU II AND I/O BOARDS The YORK Control Center is a microprocessor based The IPU and I/O boards are assembled to function as control system designed to provide the entire control a single microprocessor controller. The IPU II board for the liquid chiller.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 are supplied power for the micro board +5 V supply. KEYPAD 24 VAC is rectified, but not regulated, to provide un- The 12 button non-tactile keypad allows the user to regulated +30 VDC to supply all of the digital inputs.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 STATUS KEY 00066VIP Unit Status D A I L Y S C H E D U L E Pressing the STATUS key will enable the operator to S H U T D O W N determine current chiller operating status.
Page 126
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 The limiting pressure is a factory set limit to keep the S Y S C O O L L O A D system from faulting on the high discharge pressure S Y S C O O L L O A D...
Page 127
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 OVERRIDE is to only be used in emergencies or for S Y S L O W S U C T P R E S S servicing. Manual override mode automatically disables S Y S L O W S U C T...
Page 128
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 The internal motor protector opens at 185°F to 248°F Unit Safeties (85°C to 120°C) and auto resets. The mechanical HP Unit safeties are faults that cause all running compres- switch opens at 585 psig plus or minus 10 psig (27.92 sors to be shut down.
Page 129
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Unit Warning When the operating envelope is a standard operating envelope and the suction pressure is less than 94.0 The following messages are not unit safeties and will psig, the discharge pressure cutout will be set to 10 not be logged to the history buffer.
Page 130
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Low Superheat Cutout (EEV Mode Only) Motor Protector/High Pressure Cutout Fault The Low Superheat Cutout protects the compressors The Motor Protector/High Pressure Cutout protects the from liquid flowing back due to low suction superheat. motor from overheating or the system from experienc- This safety is only active when EEV is selected as the ing dangerously high discharge pressure.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 14 - YLAA FAULT AND INHIBIT CODES AUTO, 1X, 3X CODE TYPE FAULT OR INHIBIT DESCRIPTION (SEE LEGEND) Unit Fault Low Ambient Temperature Auto Unit Fault Low Leaving Chilled Liquid Temperature Auto Unit Fault Pump Trip (Hydro Pumps 1 or Hydro Pumps 2)
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 STATUS KEY MESSAGES General Messages Fault Messages Unit Safeties & Unit Switch Off System Safeties Warning Messages Shutdown Remote Controlled System X High Disch Pressure Low Ambient Temp Shutdown Daily Schedule Low Liquid Temp System X Low Suct Pressure Shutdown...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 DISPLAY/PRINT KEYS 00067VIP The Display/Print keys allow the user to retrieve sys- With the “UNIT TYPE” set as a liquid chiller (no tem and unit information that is useful for monitoring jumper from J11-7 to J11-12 on the I/O Board), the chiller operation, diagnosing potential problems, trou- following list of operating data screens are viewable...
Page 134
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 S Y S 7 2 . 1 P S I G C O O L I N G D E M A N D = 2 2 7 . 0 P S I G S T E P S These displays show suction and discharge pressures...
Page 135
2 message is displayed. ISN – YORK Talk via ISN allows remote load limiting and temperature reset through an ISN system. The fourth message indicates the stage of condenser fan operation that is active.
DEFROST TERMINATION TIME 3MIN BIVALENT HEAT DELAY TIME 30 MIN Current Feedback One Per System REMOTE UNIT ID PROGRAMMED YORK HYDRO KIT PUMPS 1 (410a) PUMP TOTAL RUN HOURS XXXXX (410a) * Block of information repeats for each system LD12585 UNIT DATA RETURN LIQUID TEMP 58.2 DEGF...
Page 137
MON START=00:00AM STOP=00:00AM TUE START=00:00AM STOP=00:00AM follows. WED START=00:00AM STOP=00:00AM THU START=00:00AM STOP=00:00AM FRI START=00:00AM STOP=00:00AM YORK INTERNATIONAL CORPORATION SAT START=00:00AM STOP=00:00AM MILLENNIUM LIQUID CHILLER HOL START=00:00AM STOP=00:00AM SAFETY SHUTDOWN NUMBER 1 SHUTDOWN @ 3:56PM 29 SEP 07...
Page 138
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 History Displays C O N T R O L M O D E The HISTORY key gives the user access to many unit L E A V I N G L I Q U I D and system operating parameters at the time of a unit or system safety shutdown.
Page 139
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 L E A D S Y S T E M L E A V I N G L I Q U I D T E M P S Y S T E M N U M B E R C U T O U T X X X .
Page 140
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Software Version S Y S L L S V X X X The software version may be viewed by first pressing H O T G A S S O L X X X the HISTORY key and then repeatedly pressing the ↓...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 ENTRY KEYS 00068VIP The Entry Keys allows the user to view, change pro- Enter/Adv Key grammed values. The ENTRY keys consist of an ↑ (UP) The ENTER/ADV key must be pushed after any change arrow key, ↓...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 SETPOINTS KEYS 00069VIP Programming of the cooling setpoints, daily schedule, Leaving Chilled Liquid Control and safeties is accomplished by using the keys located S E T P O I N T 4 5 .
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 center of the control range. If the control mode has The following messages illustrate both leaving chilled been programmed for RETURN LIQUID control, the liquid control and return chilled liquid control respec- message below would be displayed in place of the pre- tively.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 The LOW AMBIENT TEMP CUTOUT allows the user PROGRAM KEY to select the chiller outside ambient temperature cutout There are several operating parameters under the PRO- point. If the ambient falls below this point, the chiller GRAM key that are programmable.
Page 146
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 System Trip Volts F A N D I F F E R E N T I A L O F F P R E S S U R E X X X P S I G For individual system high current trip programming on chillers:...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Quick Reference Programming Chart Setpoints Section Cooling Setpoints Key Schedule/ Program Mode (press key to adv.) Advance Day Key (press enter to adv.) Local Leaving Mon. – Sun. Discharge Water Temp Control &...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Service Mode Use the Service Mode to view all the inputs and enable normal control. The user can disable the Service Mode or disable all the outputs on the unit, except the com- by turning on the unit switch or by powering off and on pressors.
Page 150
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 18 - PROGRAM KEY LIMITS AND DEFAULT (CONT’D) PROGRAM VALUE LOW LIMIT HIGH LIMIT OPTIONS DEFAULT (European Feature Set, Control Mode — — R-410a/R-454B) LEAVING LEAVING or RETURN (R-410a/R-454B Chiller or Condensing Unit) Hot Gas Bypass Valve Type —...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 UNIT KEYS OPTIONS CLOCK 00070VIP Options Key Option 2 – System Switches (two system units only) There are many user programmable options under the OPTIONS key. The OPTIONS key is used to scroll (Single System Display is similar) through the list of options by repeatedly pressing the S Y S...
Page 152
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Option 3 – Ambient Control Type Option 5 – Unit Control Mode A M B I E N T C O N T R O L C O N T R O L M O D E R E T U R N L I Q U I D...
Page 153
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Option 7 – Lead/Lag Type (two system units Option 9 – Manual Override Mode only) M A N U A L O V E R R I D E M O D E D I S A B L E D L E A D / L A G C O N T R O L...
Page 154
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Option 11 – Power Fail Restart Option 14 – Refrigerant Type P O W E R F A I L R E S T A R T R E F R I G E R A N T T Y P E A U T O M A T I C R –...
Page 155
P U M P S After the update is completed, an automatic reboot will When YORK HYDRO KIT PUMPS = 1, the controls occur. If an error occurred, the following message will will be closed to run the pumps whenever any one of appear with the error code and no reboot will occur.
Page 156
Option 21 – Flash Card Data Logging The displays for this PUMP SELECTION option When the following message appears, data logging is should only appear if “YORK HYDRO KIT PUMPS = disabled. 2” are selected under Option 19. Presently, this option...
Page 157
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 To change the day, time, and date press the CLOCK Option 23 – Variable Water Outlet Mode key. The display will show something similar to the When the following option is selected, the variable wa- following: ter outlet mode is enabled.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 Options Key Expansion Valve Type (press Options Key (Thermoplastic or Electric) to adv.) (Programmed under Service Display Language Mode, Viewable Only) Must be programmed for Thermostatic System Switches on/off Flash Card Update Chilled Liquid Type (water or glycol) Remote Temp Reset...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 • RS-485: connect to TB2 - Network (-1) to TB2 BACNET, MODBUS, N2, AND YORKTALK 2 COMMUNICATIONS (-1); Network (+1) to TB2 (+1) Data can be read and in some cases modified using a •...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 035-02550-xxx I/O Board LD14318 FIGURE 45 - MICRO PANEL CONNECTIONS The table below shows the minimum, maximum, and default values. TABLE 19 - MINIMUM, MAXIMUM AND DEFAULT VALUES DESCRIPTION MINIMUM MAXIMUM DEFAULT DE MODIFIER ADDRESS...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 The table below shows set-up requirements for each communication protocol. TABLE 20 - VALUES REQUIRED FOR BAS COMMUNICATION PROTOCOL SETTING DESCRIPTION BACNET MS/TP MODBUS RTU YORKTALK 2 DE MODIFIER ADDRESS 0 to 41943 0 to 41943 DE MODIFIER OFFSET...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 21 - REAL TIME ERROR NUMBERS Communications Data Map Notes ERROR (See Table 22) NUMBER DESCRIPTION 1. IPU II based units are configured for Native BAC- (##) net MS/TP and Modbus RTU communications. ALL OK E-Link Gateway not required for these two com- DATUM TYPE OK TEST FAILED...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 22 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP JOHNSON CONTROLS...
Page 164
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 22 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP (CONT’D) JOHNSON CONTROLS...
Page 165
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 22 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP (CONT’D) JOHNSON CONTROLS...
Page 166
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 TABLE 22 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP (CONT’D) JOHNSON CONTROLS...
Page 167
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 08/03/2022 YorkTalk 2 Communications Transmitted Data After receiving a valid transmission from the E-Link Received Data (Control Data) Gateway, the unit will transmit either operational data The unit receives eight data values from the E-Link or history buffer data depending on the “History Buffer Gateway.
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 SECTION 8 – UNIT OPERATION Unit Operating Sequence The operating sequence described below relates to op- 7. As the load decreases below setpoint, the com- eration on a hot water start after power has been ap- pressors will be shut down in sequence.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 08/03/2022 If after 60 seconds of run-time the leaving chilled liq- SUCTION PRESSURE LIMIT CONTROLS uid temperature is still above the Setpoint High Limit, The anticipatory controls are intended to prevent the the next compressor in sequence will be energized.
A Lead/Lag option may be selected to help equalize average run hours between systems with 2 refriger- EVAPORATOR PUMP CONTROL AND YORK ant systems. This may be programmed under the OP- HYDRO KIT PUMP CONTROL TIONS key. Auto Lead/Lag of the 2 systems based on The evaporator pump dry contacts (XTBC2 –...
DO NOT SELECT the page 180. Detailed Standard Fan Control operation option “YORK HYDRO KIT PUMPS = 2” under the is shown in Table 25 on page 181 and Table 26 on OPTIONS key. If a dual pump option is installed, the page 182.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 08/03/2022 TABLE 25 - YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (2, 3, OR 4 FANS PER SYSTEM) IPUII I/O OUTPUT FAN # CONTACTOR OFF** STAGE SYS 1 SYS 2 SYS 1 SYS 2 SYS 1...
Page 182
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 08/03/2022 TABLE 26 - YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (5 OR 6 FANS PER SYSTEM) IPUII I/O OUTPUT FAN CONTACTOR FAN # OFF** STAGE SYS 1 SYS 2 SYS 1 SYS 2 SYS 1...
There are two ways to load limit the unit. The first is through remote communication via an ISN. Load limit stages are sent through YORK Talk on pages 9 and 10 of feature 54. Page 9 is stage 1 load limit and page 10 COMPRESSOR RUN STATUS is stage 2 load limit.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 08/03/2022 If a 4 mA to 20 mA signal is supplied, it is applied to REMOTE BAS/EMS TEMPERATURE RESET Terminals A+ and A- and jumper JP1 on the I/O board USING A VOLTAGE OR CURRENT SIGNAL must be installed between pin 1 and 2.
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 SECTION 9 – SERVICE AND TROUBLESHOOTING SERVICE MODE – OUTPUTS CLEARING HISTORY BUFFERS After pressing the key sequence as described, the con- The history buffers may be cleared by pressing the trol will enter Service Mode permitting the outputs HISTORY key and then repeatedly pressing the UP (except compressors), operating hours, refrigerant arrow key until you scroll past the last history buffer...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 The analog inputs will display the input connection, TABLE 29 - I/O DIGITAL OUTPUTS the temperature or pressure, and corresponding input TB7-2 SYS 1 Compressor 1 voltage such as: TB7-3 SYS 1 Liquid Line Solenoid Valve TB7-4...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 CHECKING INPUTS AND OUTPUTS TABLE 32 - OUTDOOR AIR SENSOR TEMPERA- TURE/VOLTAGE/CORRELATION Digital Inputs VOLTAGE See the unit wiring diagram. All digital inputs are con- TEMP °F (SIGNAL INPUT TEMP °C TO RETURN) nected to J13-1 of the I/O board.
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 Each output is controlled by the microprocessor by Data Logging to Flash switching 120 VAC to the respective output connection Enabling Data Logging to Flash energizing contactors, evaporator heater, and solenoids The user can enable data logging to an SD card in the according to the operating sequence.
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 TABLE 35 - DATA LOGGING TO FLASH DATA HEADER DATA NUMBER TEXT UNIT FORMAT VALUE DESCRIPTION Date x/x/xxxx Date Time x:x:x Time (24 Hour Format) Elapsed Time Elapsed time (seconds since data logging started) LCHLT °F Leaving Chilled Liquid Temperature...
Page 194
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 TABLE 35 - DATA LOGGING TO FLASH (CONT’D) DATA HEADER DATA NUMBER TEXT UNIT FORMAT VALUE DESCRIPTION Sys 1 EEV Controller State 031-02755-001, -003 Sys 1 CSHALG_CURRENT_CYCLE_INDEX, S1 EEV Ctlr State 0 = Setup, 1 = Off, 2 = Pulldown, 3 = Controlling, 4 = Pumpdown, 5 = MOP Control 031-02755-004 S1 Dfst Temp...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 TABLE 35 - DATA LOGGING TO FLASH (CONT’D) DATA HEADER DATA NUMBER TEXT UNIT FORMAT VALUE DESCRIPTION Sys 1 CSHALG_PROPORTIONAL_CONTRIBUTION_INDEX S1 Prop Cont In (0-10000 in x100 format) Sys 1 CSHALG_INTEGRAL_CONTRIBUTION_INDEX S1 Int Cont In (0-1000000 in x10000 format) Sys 1 CSHALG_DERIVATIVE_CONTRIBUTION_INDEX...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 Assembly and Wiring Obtaining a Printout Assemble and wire all components as shown in Figure To obtain a printout, press the PRINT key on the key- 51. Strip the outside insulation back several inches and pad and then press either the OPER DATA key or HIS- individual wires about 3/8 in.
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 TROUBLESHOOTING TABLE 36 - TROUBLESHOOTING PROBLEM CAUSE SOLUTION 1. No 115 VAC to 24 VAC 1a. Check wiring and fuse 1FU. Transformer. 1b. Check wiring emergency stop contacts 5 to L of XTBC2 Terminal Block.
Page 198
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 08/03/2022 TABLE 36 - TROUBLESHOOTING (CONT’D) PROBLEM CAUSE SOLUTION 1. Improperly adjusted leaving 1. Re-program the leaving chilled liquid temp. chilled liquid temp. cutout (glycol cutout. only). 2. Micro panel setpoint/range 2.
Use YORK “V” oil 011-00949-000, when to clean than conventional round tube and fin coils. adding oil to Copeland compressor. The The reduced depth and parallel tube layout of mi- Bitzer compressor uses 011-00982-000 oil.
Page 200
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 08/03/2022 2. Rinse the coil with potable tap water. Use a gentle Cleaning Procedure Required for Standard spray from a spray nozzle with a plastic end. Do and Environment Guard Microchannel Coils not contact the coil with the hose nozzle.
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 08/03/2022 8. Visually inspect the Environment Guard Premi- THERMAL DISPERSION FLOW SWITCH um coating for any damage, degradation, or bare Check the sensor tip for buildup regularly, because it spots. If touch up of the coating is necessary, fol- can affect the sensitivity of the sensor.
Page 202
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 08/03/2022 THIS PAGE IS INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
Page 203
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 08/03/2022 TEMPERATURE CONVERSION CHART TEMPERATURE CONVERSION CHART Temperature Conversion Chart - Temperature Conversion Chart - Actual Temperatures Differential Temperatures ° F ° C °C °F ° F ° C °C °F -17.8 -0.4 -15.6 -13.3...
Page 204
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 08/03/2022 R-410A PRESSURE TEMPERATURE CHART PSIG TEMP ˚F PSIG TEMP ˚F JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 08/03/2022 The following factors can be used to convert from English to the most common SI Metric values. TABLE 37 - SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Effect (ton) 3.516 Kilowatts (kW) Power...