Electrical Data; Multiple Point Power Supply Connection - York MILLENNIUM YCAS 250 Manual

Air cooled liquid chiller
Table of Contents

Advertisement

Technical Data

MULTIPLE POINT POWER SUPPLY CONNECTION

(Two Field Provided Power Supply Circuits to the Chiller. Field Connections to Factory provided Terminal Block (Std)
or Disconnects (Opt) in the Options Panel. Circuit Breaker (Opt
FIELD PROVIDED POWER SUPPLY
CHILLER
MODEL
OVER-CURRENT
YCAS VOLTS
MIN NF
MCA
1
DISC SW
2, 9
MIN.
380
387
400
0250EC
460
320
400
575
257
400
380
477
600
0270EC
460
390
400
575
312
400
380
473
600
0300EC
460
390
400
575
311
400
380
524
600
0330EC
460
429
600
575
342
400
380
442
600
0360EC
460
365
400
575
292
400
380
473
600
0400EC
460
390
400
575
311
400
380
524
600
0440EC
460
429
600
575
342
400
See page 54 for Electrical Data footnotes.
NOTES:
1. U.L. is provided on 60 Hz units for these electrical wiring configurations.
2. — — — — — Dashed Line = Field Provided Wiring.
3. The above recommendations are based on the National Electrical Code and using copper connectors only. Field wiring must also
comply with local codes. *Group Rated breaker must be HRCR type for cU.L. machines.
50

ELECTRICAL DATA

See Note 7 (page 54)
LD04742
MULTIPLE POINT POWER SUPPLY CONNECTION
ELECTRICAL SYSTEM #1 FIELD SUPPLIED WIRING
FACTORY PROVIDED (LUGS)
WIRE RANGE
PROTECTION
STANDARD
3, 5
MAX.
4, 6
TERMINAL BLOCK
450
500
(2) # 2-300
400
400
(1)2/0-(2)4/0
300
350
(1)2/0-(2)4/0
600
700
(2) # 2-300
450
500
(2) # 2-300
350
450
(1)2/0-(2)4/0
600
600
(2) # 2-300
450
500
(2) # 2-300
350
400
(1)2/0-(2)4/0
600
700
(2)2/0-500
500
600
(2) # 2-300
400
500
(1)2/0-(2)4/0
500
600
(2) # 2-300
450
500
(1)2/0-(2)4/0
350
400
2/0 -500
600
600
(2) # 2-300
450
500
(2) # 2-300
350
400
2/0-500
600
700
(2)2/0-500
500
600
(2) # 2-300
400
450
(1)2/0-(2)4/0
Suitable for:
Across-The-Line-Start Only
Each of the two field provided power supply circuits to the
unit with individual branch circuit protection. Field Power
Wiring connections to factory provided, Non-Fused Discon-
nect Switches (Opt), or Terminal Blocks (Opt) in the Option
Box.
See Note 3
10
) in each of the two Motor Control Centers.)
COMPRESSOR #1
7
OPTIONAL NF
RLA Y-∆ ∆ ∆ ∆ ∆ LRA X-LRA RLA Y-∆ ∆ ∆ ∆ ∆ LRA X-LRA QTY FLA(EA) LRA(EA)
DISC. SWITCH
(2) 3/0-250
155
343
1,093
(2) 3/0-250
128
280
893
(2) 3/0-250
103
224
714
(2) 250-500
155
343
1,093
(2) 3/0-250
128
280
893
(2) 3/0-250
103
224
714
(2) 250-500
181
343
1,093
(2) 3/0-250
149
280
893
(2) 3/0-250
119
224
714
(2) 250-500
197
343
1,093
(2) 250-500
163
280
893
(2) 3/0-250
130
224
714
(2) 250-500
199
343
1,093
(2) 3/0-250
164
280
893
(2) 3/0-250
131
224
714
(2) 250-500
181
343
1,093
(2) 3/0-250
149
280
893
(2) 3/0-250
119
224
714
(2) 250-500
197
343
1,093
(2) 250-500
163
280
893
(2) 3/0-250
130
224
714
11, 12
FAN
COMPRESSOR #3
DATA
155
343
1,093
8
4.8
128
280
893
8
4.0
103
224
714
8
3.1
227
343
1,093
8
4.8
184
280
893
8
4.0
147
224
714
8
3.1
199
343
1,093
9
4.8
164
280
893
9
4.0
131
224
714
9
3.1
227
343
1,093
9
4.8
184
280
893
9
4.0
147
224
714
9
3.1
155
343
1,093
8
4.8
128
280
893
8
4.0
103
224
714
8
3.1
199
343
1,093
9
4.8
164
280
893
9
4.0
131
224
714
9
3.1
227
343
1,093
9
4.8
184
280
893
9
4.0
147
224
714
9
3.1
YORK INTERNATIONAL
23.0
19.0
15.2
23.0
19.0
15.2
23.0
19.0
15.2
23.0
19.0
15.2
23.0
19.0
15.2
23.0
19.0
15.2
23.0
19.0
15.2