Immergas 3.030906 Instruction And Warning Book page 7

Wireless room probe kit
Table of Contents

Advertisement

2.
ZONE ASSIGNMENT TO WIRELESS ROOM PROBE.
When installing the kit, we recommend that you follow the steps below:
1. Insert the batteries on the probe and press for 5 sec. the button on the probe.
- If the probe has already been previously Associated, the left and right LEDs will flash alternately => it is necessary to proceed with the rf disassocia- tion
(see RF Disassociation operations).
- If it is NOT Associated, the LH LED will start flashing (Right LED off) => move on to the next step of this procedure for zone assignment to wireless room
probe.
Zone assignment to wireless room probe:
1. Make sure you have correctly made the electrical connections between the concentrator and the boiler and have inserted the batteries on the wireless
probe.
2. Power the boiler and access the Menu. For more details on menu navigation and access commands, see the boiler instruction manual.
3. Implement recognition as "Service" (On the Menu\General Settings\Access level page, enter code 1122 and select access as Service).
4. Access the Zone menu.
5. Select the zone to which the room probe shall refer.
6. Enter the Configuration \ Room Probe menu.
7. Select Type = RF.
8. Set the M3 address of the concentrator to which you want to associate the wireless probe: the M3 address is defined by the position of the switches on the
card inside the concentrator (default 0).
9. Press OK => a confirmation window will appear with the text "Do You want to confirm the operation?".
10. Accept the confirmation request by pressing OK; after this action the display shows "Status ..." (association in progress) and on the concentrator the left LED
flashes (waiting for association)
11. Within 30 seconds, move to the probe to be associated and press the central button for 5 seconds. When the LH LED flashes, briefly press the button
again (1 second).
12. On the probe, once the operation has been completed correctly, the 2 left and right LEDs will be flashing alternately for 10 sec.. Then the number of the
associated zone will be indicated on the left LED through flashes, but with the right LED steady. If the operation is not completed correctly, the two LEDs
will be flashing at the same time for 5 seconds and the text "No-Link Status" shall appear on the display (it is therefore necessary to repeat the operation)
13. On the Display, once the operation has been completed correctly, the room probe status appears as "ok".
Attention: with a short press, if it lasts more than 1 second, the operation is unsuccessful.
2.1 DISPLAYABLE INDICATIONS ON THE MENU UNDER THE ITEM "ROOM PROBE STATUS"
The following items appear in the Room probe association window
• Status= Err: configuration error; on the concentrator the association se-quence was not successful. Repeat the association sequence.
• Status = No link: error on RF association between probe and concentrator; it may also appear with low battery. Check wireless probe operation and
repeat the association sequence.
• Status = - - : indicates the waiting for configuration; if it is maintained for a long time during the association sequence, check the connection between
concentrator and boiler.
• Status = ... : indicates "association in progress" mode
• Status = ok: indicates the correct association between wireless probe and the zone to be checked.