SolarEdge SE K Series Installation Manual page 72

Three phase inverters with synergy technology
Hide thumbs Also See for SE K Series:
Table of Contents

Advertisement

Figure 34: RS485 terminal block on the communication board
 4. Loosen the screws of pins A(+), B(-), and G on the left of the RS485 terminal block
(RS485-1 or RS485-2).
 5. Insert the wire ends into the G, A and B pins shown above. Use Four- or six-wire
twisted pair cable for this connection.
You can use any color wire for each of the A, B and G connections, as long as:
The same color wire is used for all A pins the same color for all B pins and the
same color for all G pins
The wire for G is not from the same twisted pair as A or B.
 6. For creating an RS485 bus - connect all B, A and G pins in all inverters. The following
figure shows this connection schema:
Three Phase Inverters with Synergy Technology PN: SExxK-xxxxIxxxx
Chapter 5: Setting Up Communication with the Monitoring
Figure 35: RS485 terminal block
Platform   71