  Connecting Ground and AC Wires to the Synergy Manager
Bolt hole diameter size: 0.5"
Compression lugs of the one-hole, standard barrel, 600V type.
Maximum wire size: 4/0 AWG 120 mm
Maximum lug tongue thickness: 0.27 "
Maximum lug tongue width: 1.29 "
 7. Use heat shrink to isolate the lug barrels.
 8. Remove the nut of the AC terminals.
 9. Connect the lug of the AC wires according to the labels on AC terminal block. Fasten
the nut of the AC terminals to a torque of 15.4 lb.*ft.
NOTE
right: L1 → L2 → L3 → N (See Figure 28 ).
For easy installation of the AC wires, start connecting the wires from left to
 10. Place the upper cover of the AC terminal block and push until a lock click is heard.
Close the Synergy Manager cover and secure it by tightening the six screws to a
torque of lb*ft2.6.
Figure 28: Connecting AC wires to the AC terminals
Three Phase Inverters with Synergy Technology PN: SExxK-xxxxIxxxx
2