41
Drilling Conduit Holes
AC connector: for supply of AC power to the Synergy Manager
Drilling Conduit Holes
This section describes how to drill AC and DC openings at the bottom of the Synergy
Manager for connecting the AC and DC conduits.
This procedure must be performed before mounting the Synergy Manager.
To open conduit drill guides:
1. Ensure that the Safety Switch is set to OFF (0) and ON/OFF/P switch of the Synergy
Manager is in OFF position.
2. Remove the screws securing the DC and AC panels and remove the panels from the
bottom of the Synergy Manager enclosure.
CAUTION!
To avoid damage to the internal part of the Synergy Manager, always
remove the panels from unit before drilling holes.
NOTE
Unused conduit openings should always be sealed.
Figure 14: Synergy Unit Interface Connectors
Three Phase Inverters with Synergy Technology PN: SExxK-xxxxIxxxx