Function
OLRT
Active Power-Reactive
(1)
power mode
P3
P2
P1
P'1
P'2
P'3
Q3
Q2
Q1
Q'1
Q'2
Q'3
Voltage Active power
mode
(1)
V1
P1
V2
P2
P'2
OLRT
Frequency-droop mode
DBOF
DBUF
KOF
KUF
OLRT
Normal Ramp Rate
(1)
Load parameters P' and Q' apply to single phase energy storage inverters only.
(2)
California rule 21 function.
Three Phase Inverters with Synergy Technology PN: SExxK-xxxxIxxxx
IEEE 1547 Default Settings
Disabled
Disabled
Disabled
(2)
Appendix E: Interconnection
5
1
0.5-1 nameplate power p.u.
0.5
0.4-0.8 nameplate power p.u.
0.2
0-0.7 nameplate power p.u.
-0.2
-0.5
-0.4-(-0.8) namplate load p.u.
-1
-1-(-0.5) namplate load p.u.
-0.44
0
0
0
0
0.44
1.06
1
1.1
0
0
10
0.036
0.036
0.05
0.05
5
100
Standards   101
Range
1-90 seconds
-0.7-0 nameplate load p.u.
+/- 1 nameplate Var p.u.
+/- 1 nameplate Var p.u.
+/- 1 nameplate Var p.u.
+/- 1 nameplate Var p.u.
+/- 1 nameplate Var p.u.
+/- 1 nameplate Var p.u.
1.05-1.09 V p.u.
nameplate power p.u.
1.06-1.10 V p.u.
0-1 namplate power p.u.
-1-0 nameplate load p.u.
0.5-60 seconds
0-1 Hz
0-1 Hz
0.02-0.07
0.02-0.07
0.2-10 seconds
1-100%/ seconds