100
Enter Service Settings
Utility authorization is required to change abnormal voltage and frequency set-points.
Response to abnormal conditions and untentional islanding results in a disconnect of
the equipment from the area EPS.
Enter Service Settings
Function
Enter Service Delay
Enter Service Ramp Period
Minium voltage
Maxium voltage
Minium frequency
Maxium Frequency
Grid Support Functions
Function
Constant Power Factor
mode
Constant Reactive power
mode
Voltage-Reactive power
mode
V2
Q2
V3
Q3
V1
Q1
V4
Q4
Settings will be specified by the regional EPS (electric power system) operator.
(1)
(2)
Changes to this setting should not be made without approval from the area EPS operator
IEEE 1547 Default Settings
IEEE 1547 Default Settings
1
Disabled
Disabled
0.98
0
1.02
0
0.92
0.44
1.08
-0.44
Three Phase Inverters with Synergy Technology PN: SExxK-xxxxIxxxx
(1)
(2)
300
100
0.917
1.05
59.5
60.1
(1)
+/- 1 nameplate Var p.u.
0.92 -1.05 V p.u.
+/- 1 nameplate Var p.u.
0.95 -1.08 V p.u.
+/- 1 nameplate Var p.u.
0.77-1.03 V p.u.
0-1 nameplate Var p.u.
0.97-1.23 V p.u.
(-1)-0 nameplate Var p.u.
Range
0-1000 seconds
1-1000 seconds
0.88-0.95 p.u.
1.05 -1.05 p.u.
59.0-59.9 Hz
60.1-61.0 Hz
Range
0-1