Immergas 3.021525 Instruction And Warning Book page 19

In-line electric heater
Table of Contents

Advertisement

Available languages

Available languages

2.10
WIRING DIAGRAM.
Legend:
BK - Black
BN - Brown
BU - Blue
GNYE - Green / Yellow
GY - Grey
OG - Orange
RD - Red
VT - Violet
WH - White
2.11
TECHNICAL DATA.
Heater
Electric supply
Max. total intensity
General protection (not supplied)
Supply cable
Heat pump <=> kit connection cable
Power
Max. working pressure
Working temperature
Max. temperature
Weight
IE
KC1 - Heater stage 1 relay
KC2 - Heater stage 2 relay
FCA - High temperature automatic reset cut-cut
FCM - High temperature manual reset cut-cut
ICS - enable switch
HCS - operating light
R - electric heater
6 KW
230V - 50Hz single phase +
ground
31.5A
32A
3G6
2G1
3x2000 W - 230 V
19
6KW
400V - 50Hz three phase + N +
ground
10.5A
12A
5G1.5
2G1
3 bar
65 °C
90 °C
8 kg
9