INSTALLATION SITE.

installed indoors, an additional refrigerant detection device must be added in addition to a further ventilation appliance
pursuant to standard EN378. Make sure to take adequate measures so that the unit is not used to house small animals.
• Animals that come into contact with electric components could cause operating failures, smoke or re. Please advise
the customer to keep the area around the unit clean.
hoose an installation site where the following conditions are met and which is approved by the customer.
- Well ventilated places.
- Places where the unit does not bother neighbours.
- Safe places that can bear the weight and vibrations of the unit and where it can be installed on a at surface.
- Places where ammable gas or ammable product leaks are not possible.
-
e appliance is not intended to be used in potentially explosive atmospheres.
- Places where clearance for maintenance can be guaranteed.
- Places where the pipes and lengths of the wiring of the units are within the admissible limits.
- Places where the water escaping the appliance cannot damage the environment (e.g. in case of blocked drain pipe).
- Places where rain can be prevented as far as possible.
- Do not install the unit in places which are o en used as workspace. In case of construction work (for example grinding,
etc.) which creates lots of dust, the appliance must be covered.
- Do not place any object or equipment above the unit (top plate).
- Do not climb, sit or stand on the unit.
- Make sure that su cient precautions are taken in case of refrigerant leaks according to local laws and regulations on the
matter.
- Do not install the unit near the sea or in the presence of corrosive gas.
• When the unit is installed in a place exposed to strong wind, pay particular attention to the following.
Strong winds 5 m/sec or more that blow against the air outlet of the unit cause a short circuit (suction of exhaust air)
which could have the following consequences.
- Deterioration of operating capacity.
- Frequent acceleration of icing in heating mode.
- Interruption of operation due to the high pressure increase.
- When a strong wind continuously blows on the front of the unit, the fan can begin to spin so quickly that it breaks.
Under normal conditions, refer to the following gures for installation of the units 4-16 kW:
4-6 kW
8-16 kW
A
≥ 300 mm
≥ 300 mm