Supervision
System Error
Operation or protection anomaly
Code
Code
E8
9
Water ow fault.
Error of compressor intake tempera-
E9
10
ture sensor (
Error of compressor drain tempera-
EA
11
ture sensor (Tp).
Error of solar panel temperature
Eb
12
sensor (Tsolar).
Error of low temperature sensor
EC
13
(Tbt2) of the thermostat manifold.
Error of inlet water temperature sen-
Ed
14
sor (Tw_in) of plate heat exchanger.
EEPROM fault of the main control
EE
15
board of hydraulic module.
Leakage fault on tank booster heater
EP
19
(TBH).
Check that all the shut-o valves of the water circuit are completely
open.
1. Check whether the water lter needs to be cleaned.
2. Chap. 9.5 Filling with water.
3. Make sure there is no air in the system (de-aeration).
4. Check the pressure of the water.
5. Check that the pump speed is set at the maximum speed.
6. Make sure that the expansion vessel is not damaged.
7. Check that the pressure drops of the hydraulic circuit are not too
high for the pump (Chap. 10.4
8. If this error occurs during defrosting (during space heating or
domestic hot water heating), make sure that the power supply of the
backup heater is wired correctly and that the fuses are not blown.
9. Check that the fuse of the pump and the fuse of the PCB are not
blown.
1. Check the sensor resistance.
2.
3.
).
the water, dry the connector. Add waterproof adhesive.
4. Fault of sensor
1. Check the sensor resistance.
2.
3.
the water, dry the connector. Add waterproof adhesive.
4. Fault of sensor Tp, replace it with a new sensor.
1. Check the sensor resistance.
2.
3.
move the water, dry the connector. Add waterproof adhesive.
4. Fault of sensor Tsolar, replace it with a new sensor.
1. Check the sensor resistance.
2.
3.
e connector of sensor Tbt2 is wet or there is water inside. Remove
the water, dry the connector. Add waterproof adhesive.
4. Fault of sensor Tbt2, replace it with a new sensor.
1. Check the sensor resistance.
2.
3.
move the water, dry the connector. Add waterproof adhesive.
4. Fault of sensor Tw_in, replace it with a new sensor.
1.
2.
ponent.
3.
e main control board of the hydraulic module is damaged, replace
it with a new PCB.
Check device connected to the TBH outputs.
Cause of fault and corrective action
e connector of sensor
is loose. Reconnect it.
e connector of sensor
is wet or there is water inside. Remove
, replace it with a new sensor.
e connector of sensor Tp is loose. Reconnect it.
e connector of sensor Tp is wet or there is water inside. Remove
e connector of sensor Tsolar is loose. Reconnect it.
e connector of sensor Tsolar is wet or there is water inside. Re-
e connector of sensor Tbt2 is loose. Reconnect it.
e connector of sensor Tw_in is loose. Reconnect it.
e connector of sensor Tw_in is wet or there is water inside. Re-
e EEprom parameter is in error, rewrite the EEprom data.
e EEprom component is damaged, replace the EEprom com-
e water pressure must be >1 bar.
e circulation pump).