9.16 SYSTEM MANAGER - EXPANSION COMMUNICATION CABLE CONNECTION.

Key:
A13 - System manager
A15 - Expansion
F - Function
I - Expansion Addresses
Z1 - Zone 1
Z2 - Zone 2
Z3 - Zone 3
F1 - Special functions 1
Note: - Use shielded cable for RS485 line if installing the equipment in a household environment.
- The maximum distances allowed between expansion and system manager depend on the type of cable
and resistance as follows:
- With telephone cable with resistance ≤ 0.14 (W/m) max distance 600 m;
- With telephone cable with resistance ≤ 0.25 (W/m) max distance 400 m;
- With shielded cable AWG24 with resistance ≤ 0.078 (W/m) max distance 600 m;