Audax Configuration - Immergas System Manager Kit Instructions And Warnings

Electronic control
Hide thumbs Also See for System Manager Kit:
Table of Contents

Advertisement

8.1.5 Audax configuration

This heat pump family includes the following models:
- Audax 6
- Audax 8
- Audax 12
- Audax 16
- Audax 16 Mono
- Audax Top 18 ErP
- Audax Top 21 ErP
With these machines, the circulation pumps operation
logic can be configured.
The parameters are:
- Mode (P33). Enable the pump operation with speed set
"Max.speeed" or the modulating mode with tracking
of the "Modulating" temperature differential.
- Minimum Speed (P33). Value of minimum speed used
in modulating operation.
- Maximum Speed (P33). Value of maximum speed
used in modulating operation.
- Delta T (P33). Temperature delta to be maintained
with modulating operation.
A machine power reduction can be set.
The parameters are:
- Anti-lock circ. (P34) Enable HP anti-lock circulator.
- Flow switch (P34):
- 0= flow switch function Type 0;
- 1= flow switch function Type 1
- Enabling reduction (P34). Enables a reduction in the
operating frequency of the HP, which is controlled by
defining the reduced operating schedule from the user
menu.
- Power in reduced (P34). Power percentage in reduc-
tion mode.
N.B.: reduction mode must also be enabled via the
terminal block.
If main machine board is replaced, performing the
parameterisation operation is required.
The parameters are:
- Model (P41). Select the Heat pump model to para-
metrise.
- Configure (P41). Select "Yes" to start parameterisation.
- Orientation. In presence of several heat pumps com-
municating with each other, setting the machines with
different addresses is required.
Machine
Heat pump 1
Heat pump 2
Heat pump 3
Heat pump 4
Turn off all machines on the same communication bus
except the one to be configured.
You must set the addresses as follows:
- Type (P45): select the heat pump type.
- Audax
- New address to be assigned (P45). Set the current
address of the machine (value between 12 and 14 based
on heat pump no.).
- Configure (P45). Select YES to start address configu-
ration process.
In case of configuration problems, the initial address of
a machine can be restored (address 11).
- Type (P46): select the heat pump type.
- Audax
- Current address (P46). Set the current address of the
machine (value between 12 and 14 based on heat pump
no.).
- Configure (P46). Select YES to start address configu-
ration process.
Certain manual functions of the machine can be enabled.
The parameters are:
- Circ.pump.override (A21). Enables the circulation
pump to be manually overridden at the set speed.
- Flow switch (A21). Displays flow switch status.
- Mode (A22). Heat pump operation override (all con-
trols on the flow and return sensors are disabled with
these modes).
- Off
56 56
Address
11
12
13
14