5.9

SUPERVISOR.

In this section it is possible to set the type of supervision
of the system management kit.
There are two types of supervision: digital and with
communication protocol.
You can control the system through digital inputs on
expansion 5. Contact the technical assistance for further
information.
- Enable (B01). The digital supervision function is
enabled.
If this mode is activated you must insert the RS485
communication card in the appropriate housing called
"serial card 1" (optional).
- Protocol (B02). Set on Modbus / Carel / Winload
- Band Rate (B02). 1200 / 2400 / 4800 / 9600 / 19200
- Address (B02). Set Modbus address of manager. Con-
tact the technical assistance for further information.
If this mode is activated you must insert the RS485
communication card in the appropriate housing called
"serial card 2" (optional).
- Protocol (B03). Set on Modbus / Carel / Winload
- Band Rate (B03). 1200 / 2400 / 4800 / 9600 / 19200
- Address (B03). Set Modbus address of manager. Con-
tact the technical assistance for further information.
Dominus (Optional) (B04).
It is possible to control the system remotely, by using the
optional Dominus kit (version 2.0 or later).
Connect to the appliance as shown (Electrical Diagram
Parag. 9.35).
For further information consult the relative instruction
sheet.

5.10 TELEPHONE DIALLER.

Using digital supervision, illustrated in the previous
paragraph, it is possible to use a telephone dialler to
manage system operational modes. For connections, see
the related electrical diagram.

5.11 RESET COUNTER.

In this section it is possible to reset the operation hour
counter for the heat pump, the source of integration, and
solar circuit 1 and 2.
Press the arrows
(R01).
Press the
button to enter the submenu.

5.12 MANUAL MANAGEMENT.

In this section it is possible to, based on the selected
configuration, enable or disable the various available
controls.
Press the arrows
Press the
button to enter the submenu.
When you exit the menu any enabled commands are
reset.
In the Cooling Test (A22) and Heating Test (A22) modes
the Set Freq. corresponds to the maximum operating
frequency of the machine.
In the Ramp Cooling Test and Ramp Heating Test modes,
the Set Freq. corresponds to the slope of the frequency
with which the machine is activated (Hz / min).
N.B.: in the Ramp Tests the Set Freq value can take
negative
values.
26 26
and select "Reset Counter"
and select "Manual".